IB IL IMPULSE-IN-2MBD

Product ID:19129
Updated: 2026/4/6
Phoenix Contact IB IL IMPULSE-IN-2MBD

Key Features

  • 1Supports incremental encoders with symmetrical and asymmetrical signals.
  • 2Three digital inputs for connecting limit switches or home position switches.
  • 3Precise evaluation via 1x, 2x, or 4x sampling.
  • 4Direction of rotation indicator via LED.
  • 5Transmission speed of 2 Mbps via inline local bus.
Product Details
IB IL IMPULSE-IN-2MBD
Phoenix Contact

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
Color
green
Connection method
Inline data jumper
Transmission speed
2 Mbps
ID code (dec.)
95
ID code (hex)
5F
Length code (hex)
02
Length code (dec)
133
Process data channel
32 bit
Input address area
4 Byte
Output address area
4 Byte
Register length
32 bit
Required parameter data
6 Byte
Number of inputs
1
Common mode voltage range signal - ground
-10 V ... 13.2 V
Length measuring range
> 0 mm ... 3850 mm (Resolution: 5 µm)
Ultra-sound speed (gradient)
2500 m/s ... 2999.99 m/s (Firmware 1.22 and higher) 2750 m/s ... 2898 m/s (Firmware 1.21 and higher)
Product type
I/O component
Product family
Inline
Type
modular
Encoder supply voltage
24 V
Encoder supply current
max. 250 mA
Supply voltage
7.5 V (via voltage jumper)
Current draw
max. 100 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
typ. 150 mA (with connected sensor)
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
75 % ... 85 %
Permissible humidity (storage/transport)
75 % ... 85 %
Mounting type
DIN rail mounting

Specifications may be subject to change without notice