IB IL SGI 2/F-2MBD-PAC

Product ID:19210
Updated: 2026/4/3
Phoenix Contact IB IL SGI 2/F-2MBD-PAC

Key Features

  • 1Fast Inputs for Strain Gauges: Equipped with 2 quick inputs for strain gauges.
  • 26- and 4-Wire Connection: Supports both 6- and 4-wire connection methods for strain gauges.
  • 3Sensor Supply Voltage: Provides sensor supply voltage, eliminating the need for an external power supply.
  • 4Process Data Operation: Communicates via process data or parameter channel (PCP) for efficient data transfer.
  • 5Diagnostic Indicators: Features diagnostic and status indicators for easy monitoring and troubleshooting.
Product Details
IB IL SGI 2/F-2MBD-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Width
48.8 mm
Height
136 mm
Depth
71.5 mm
Note on application
Only for industrial use
Number of interfaces
2
Connection method
Inline data jumper
Transmission speed
2 Mbps
Transmission physics
Copper
ID code (dec.)
223
ID code (hex)
DF
Length code (hex)
03
Length code (dec)
03
Process data channel
48 bit
Input address area
6 Byte
Output address area
6 Byte
Register length
32 bit
Required parameter data
15 Byte
Required configuration data
5 Byte
Description of the input
Input channels for strain gauge
Number of inputs
2
Connection technology
6 or 4-wire, twisted pair shielded cable
Bridge difference U
Measuring range specified by selecting the characteristic and the bridge voltage
Bridge voltage U
3.3 V 5 V
Measured value representation
15 bit + sign bit
Characteristics
±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V +1 mV/V, +2 mV/V, +3 mV/V, +4 mV/V
Output description
Voltage output
Number of outputs
2
Impedance
> 58.3 Ω (typical; permissible total resistance of the strain gauge)
Output voltage
5 V 3.3 V
Output current
typ. 55 mA (with U typ. 85 mA (with U
Product type
I/O component
Product family
Inline
Type
modular
Scope of delivery
including Inline connectors and marking fields
Operating mode
Process data operation with 3 words, PCP with 1 word
Special properties
2 fast inputs 4-, 6-conductor connection technology
Diagnostics messages
Failure of the power supply at U Failure of or insufficient communications power U I/O error Error message in the process data
Article revision
07
Maximum power dissipation for nominal condition
1.25 W
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 110 mA typ. 100 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
typ. 32 mA (with maximum load of 58.3 Ω when U typ. 8 mA (without strain gauge)
Test voltage: Logic/analog I/O (digital isolator)
500 V AC, 50 Hz, 1 min
Test voltage: Functional ground/analog I/O (isolating distance)
500 V AC, 50 Hz, 1 min
Test voltage: Logic/functional ground (isolating distance)
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice