IB IL TEMP 2 UTH/CG-PAC

Product ID:17522
Updated: 2026/8/4
Phoenix Contact IB IL TEMP 2 UTH/CG-PAC

Key Features

  • 1High Accuracy Measurement: Measures signals from conventional thermocouples and resistance thermometers with 16-bit resolution.
  • 2Configurable Temperature Measurement: Supports absolute and differential temperature measurement, configurable for various applications.
  • 3Versatile Sensor Compatibility: Compatible with U, T, L, J, E, K, N, S, R, B, C, W, HK thermocouples.
  • 4Durable Design: Operates in ambient temperatures from -25°C to 55°C and up to 95% humidity.
  • 5Easy Installation: Includes accessories like labeling fields and inline shield connectors for easy setup and customization.

Need price and lead time?

Request a quote for original Phoenix Contact IB IL TEMP 2 UTH/CG-PAC. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original Phoenix Contact
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Color
green
Connection method
Inline data jumper
Transmission speed
500 kbps
Transmission physics
Copper
ID code (dec.)
127
ID code (hex)
2F
Length code (hex)
02
Length code (dec)
02
Process data channel
32 bit
Input address area
4 Byte
Output address area
4 Byte
Register length
32 bit
Required parameter data
6 Byte
Required configuration data
4 Byte
Input name
Analog UTH inputs
Description of the input
Inputs for thermocouples or linear voltage
Number of inputs
2
Connection method
Spring-cage connection
Connection technology
2-conductor (shielded)
A/D conversion time
< 120 µs (per channel)
A/D converter resolution
16 bit
Sensor types that can be used (TC)
U, T, L, J, E, K, N, S, R, B, C, W, HK
Measuring principle
Successive approximation
Measured value representation
16 bits two's complement and other
Process data update
30 ms (For both channels)
Product type
I/O component
Type
modular Inline
Operating mode
Process data operation with 2 words
Supply voltage
7.5 V DC (via voltage jumper)
Current draw
max. 60 mA typ. 43 mA
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 18 mA typ. 11 mA
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC, 50 Hz, 1 min
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min 500 V AC, 50 Hz, 1 min
Test voltage: 24 V analog supply (analog I/O)/functional ground
500 V AC, 50 Hz, 1 min
Test voltage: 24 V supply (I/O) / functional ground
500 V AC, 50 Hz, 1 min
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 55 °C
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice