IL EIP BK DI8 DO4 2TX-XC-PAC

Product ID:19276
Updated: 2026/4/6
Phoenix Contact IL EIP BK DI8 DO4 2TX-XC-PAC

Key Features

  • 1EtherNet/IP™ Compatibility: Supports EtherNet/IP™ protocol for seamless integration into industrial networks.
  • 2High-Performance I/Os: Features 8 digital inputs and 4 digital outputs with 500 mA capacity.
  • 3Web-Based Management: Easy configuration and monitoring via web-based interface.
  • 4Robust Connectivity: Includes 2 RJ45 connections for reliable data transmission.
  • 5Industrial-Grade Design: Designed for harsh environments with IP20 protection and DIN rail mounting.
Product Details
IL EIP BK DI8 DO4 2TX-XC-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Width
80 mm
Height
119.8 mm
Depth
71.5 mm
Note on dimensions
Specfications with connectors
Color
green
Number of interfaces
2
Connection method
RJ45 jack
Note on the connection method
Auto negotiation and autocrossing
Permissible conductor cross section
0.14 mm² ... 0.22 mm² (twisted pair)
Transmission speed
10/100 Mbps (half or full duplex (automatic detection))
Transmission physics
Ethernet in RJ45 twisted pair
Connection method
Inline data jumper
Transmission speed
500 kbps / 2 Mbps (automatic detection, no combined system)
Max. number of local bus devices
61 (The on-board I/Os are two devices)
Number of supported devices
max. 63 (per station)
Number of local bus devices that can be connected
max. 61 (The on-board I/Os are two devices)
Number of devices with parameter channel
max. 8
Number of supported branch terminals with remote bus branch
0
ID code (hex)
none
Input address area
8 bit
Output address area
4 bit
Register length
16 bit
Input name
Digital inputs
Description of the input
EN 61131-2 type 1
Number of inputs
8
Connection method
Inline connector
Connection technology
3-conductor
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input voltage U
24 V DC
Nominal input current at U
typ. 3 mA
Typical input current per channel
typ. 3 mA
Typical response time
approx. 500 µs
Delay at signal change from 0 to 1
1.2 ms
Delay at signal change from 1 to 0
1.2 ms
Protective circuit
Reverse polarity protection; Suppressor diode
Output name
Digital outputs
Connection method
Inline connector
Connection technology
3-conductor
Number of outputs
4
Protective circuit
Short-circuit and overload protection; Freewheeling circuit in the output driver
Output voltage
24 V DC -1 V (At nominal current)
Maximum output current per module
max. 2 A
Nominal output voltage
24 V DC
Output current when switched off
max. 10 µA (When not loaded, a voltage can be measured even at an output that is not set.)
Nominal load, inductive
12 VA (1.2 H, 48 Ω)
Nominal load, lamp
12 W
Nominal load, ohmic
12 W
Reverse voltage resistance to short pulses
Reverse voltage proof
Behavior with overload
Auto restart
Behavior with inductive overload
Output can be destroyed
Behavior at voltage switch-off
The output follows the power supply without delay
Signal delay
typ. 1.2 ms
Overcurrent shut-down
min. 0.7 A
Product type
I/O component
Product family
Inline
Type
modular Inline
Scope of delivery
including Inline connectors and marking fields
No. of channels
12
Special properties
Extreme conditions version
Diagnostics messages
Short-circuit or overload of the digital outputs yes Sensor supply failure yes Failure of the actuator supply yes
Article revision
02
Power dissipation
typ. 1.7 W (entire device)
Protective circuit
Short-circuit protection of the communications power; electronic Short-circuit protection of the analog supply; electronic
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 0.98 A min. 80 mA (without connected I/O terminal blocks)
Supply voltage
7.5 V DC
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 8 A DC min. 3 mA (without sensors)
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 8 A DC min. 6 mA (without actuators)
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Ambient temperature (operation)
-25 °C ... 60 °C (Standard) -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protection
IP20
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice