140ACI03000C

Product ID:23739
Updated: 2026/4/3
schneider 140ACI03000C

Key Features

  • 1Acquire data precisely with 8 analog input channels and 12-bit resolution. 2、Support multiple linear ranges from 1-5V to 4-20mA for sensor flexibility. 3、Ensure reliable performance in demanding industrial environments with robust construction. 4、Process signals accurately using built-in conditioning for consistent readings. 5、Integrate seamlessly with Modicon Quantum systems and diverse sensor types.
Product Details
140ACI03000C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Analogue input module
Type of filter
Single pole low pass - 3 dB at 15 Hz +/- 20 %
Analogue input number
8
input type
Differential
Addressing requirement
9 input words
Analogue input resolution
12 bits
Linear measuring range
1...5 V<br />4...20 mA
Absolute maximum input
50 V DC<br />25 mA
Input impedance
250 Ohm current +/- 0.01 %<br />> 20 MOhm voltage
Absolute accuracy error
+/- 0.05 % of full scale<br />+/- 0.1 % of full scale maximum
Linearity error
+/- 0.04 %
Accuracy drift according to temperature
+/- 0.0025 % of full scale/°C<br /><= 0.005 % of full scale/°C
Common mode rejection
> - 72 dB 60 Hz
Isolation between channels and bus
1000 V DC<br />3000 V DC 60 s
Isolation between channels
30 V DC
Update time
5 ms
Fault type
Broken wire 4...20 mA<br />Undervoltage range 1...5 V
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault 1 LED (red)<br /> for channel is turned on 8 LEDs (green)<br /> for channel fault 8 LEDs (red)
Bus current requirement
240 mA
Power dissipation in W
2 W
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
UL 508<br />CSA C22.2 No 142
Product Certifications
FM Class 1 Division 2<br />cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice