140CPS11420C
Product ID:31672
Updated: 2026/4/4

Key Features
- 1Deliver stable power output with internal overvoltage and overload protections. 2、Adapt to system needs with summable or standalone configurations. 3、Ensure compatibility with 115V AC and 230V AC input voltages. 4、Provide clean power with low harmonic distortion (≤10%). 5、Meet CE standards for safety in industrial environments.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Power supply module |
| power supply type | Summable or standalone | Input voltage | 115 V 93...132 V) AC 47…63 Hz<br />230 V 170...276 V) AC |
| Input current | 1300 mA 115 V<br />750 mA 230 V | Inrush current | 19 A 230 V<br />38 A 115 V |
| Rated power in VA | 130 VA | Associated fuse rating | 2 A, slow-blow |
| Harmonic distortion | <= 10 % of fundamental rms value | Output voltage | 5.1 V DC |
| Power supply output current | 11 A 140 °F (60 °C) standalone<br />20 A 140 °F (60 °C) summable | Output overvoltage protection | Internal |
| Output overload protection | Internal | Power dissipation | 6 + (1.5 x Iout) where Iout is in A |
| Alarm output | 1 NC 6 A 220 V power supply fault | Local signalling | for power (PWR OK) 1 LED (green) |
| marking | CE | Module format | Standard |
| Net Weight | 1.43 lb(US) (0.65 kg) | Protective treatment | Conformal coating Humiseal 1A33 |
| Standards | CSA C22.2 No 142<br />UL 508 | Product Certifications | cUL |
| Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice