140CPS12400C
Product ID:31674
Updated: 2026/4/4

Key Features
- 1Ensure continuous operation with backup power during primary source failures. 2、Support a wide input voltage range of 115V and 230V AC for global compatibility. 3、Handle high inrush currents up to 38A at 115V to protect system integrity. 4、Safeguard equipment with built-in overvoltage and overload protection circuits. 5、Meet European safety standards with CE certification for international markets.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Power supply module |
| power supply type | Redundant | Input voltage | 115 V 93...138 V) AC 47…63 Hz<br />230 V 170...276 V) AC |
| Input current | 1100 mA 115 V<br />600 mA 230 V | Inrush current | 19 A 230 V<br />38 A 115 V |
| Rated power in VA | 130 VA | Associated fuse rating | 2 A, slow-blow |
| Harmonic distortion | <= 10 % of fundamental rms value | Output voltage | 5.1 V DC |
| Power supply output current | 8 A 140.0000000000 °F (60 °C) redundant | Output overvoltage protection | Internal |
| Output overload protection | Internal | Power dissipation | 6 + (1.5 x Iout) where Iout is in A |
| Local signalling | for power (PWR OK) 1 LED (green) | marking | CE |
| Module format | Standard | Net Weight | 1.43 lb(US) (0.65 kg) |
| Protective treatment | Conformal coating Humiseal 1A33 | Standards | CSA C22.2 No 142<br />UL 508 |
| Product Certifications | FM Class 1 Division 2<br />cUL | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |