140CPS12400C

Product ID:31674
Updated: 2026/4/4
schneider 140CPS12400C

Key Features

  • 1Ensure continuous operation with backup power during primary source failures. 2、Support a wide input voltage range of 115V and 230V AC for global compatibility. 3、Handle high inrush currents up to 38A at 115V to protect system integrity. 4、Safeguard equipment with built-in overvoltage and overload protection circuits. 5、Meet European safety standards with CE certification for international markets.
Product Details
140CPS12400C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Power supply module
power supply type
Redundant
Input voltage
115 V 93...138 V) AC 47…63 Hz<br />230 V 170...276 V) AC
Input current
1100 mA 115 V<br />600 mA 230 V
Inrush current
19 A 230 V<br />38 A 115 V
Rated power in VA
130 VA
Associated fuse rating
2 A, slow-blow
Harmonic distortion
<= 10 % of fundamental rms value
Output voltage
5.1 V DC
Power supply output current
8 A 140.0000000000 °F (60 °C) redundant
Output overvoltage protection
Internal
Output overload protection
Internal
Power dissipation
6 + (1.5 x Iout) where Iout is in A
Local signalling
for power (PWR OK) 1 LED (green)
marking
CE
Module format
Standard
Net Weight
1.43 lb(US) (0.65 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
FM Class 1 Division 2<br />cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice