140CPS12420C

Product ID:31676
Updated: 2026/4/4
schneider 140CPS12420C

Key Features

  • 1Ensure continuous operation with dual power sources for reliability. 2、Support 230V AC and 115V AC with a 47-63 Hz frequency range. 3、Provide 11A in standalone mode and 10A in redundant mode. 4、Maintain less than 10% harmonic distortion for stable power. 5、Equip with overvoltage and overload protection for safety.
Product Details
140CPS12420C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Power supply module
power supply type
Redundant
Input voltage
115 V 93...138 V) AC 47…63 Hz<br />230 V 170...276 V) AC
Input current
1100 mA 115 V<br />600 mA 230 V
Inrush current
19 A 230 V<br />38 A 115 V
Rated power in VA
130 VA
Associated fuse rating
2 A, slow-blow
Harmonic distortion
<= 10 % of fundamental rms value
Output voltage
5.1 V DC
Power supply output current
11 A 140 °F (60 °C) standalone<br />10 A 140 °F (60 °C) redundant
Output overvoltage protection
Internal
Output overload protection
Internal
Power dissipation
6 + (1.5 x Iout) where Iout is in A
Alarm output
1 NC 6 A 220 V power supply fault
Local signalling
for power (PWR OK) 1 LED (green)
marking
CE
Module format
Standard
Net Weight
1.43 lb(US) (0.65 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice