140CPS21400
Product ID:31679
Updated: 2026/4/4

Key Features
- 1Ensure stable operation with a 24 V DC input voltage range (20-30 V) and a 5.1 V DC output voltage. 2、Support multiple devices with an 8 A summable output current for optimized power distribution. 3、Protect connected devices with internal output overvoltage and overload protection. 4、Minimize heat generation with calculated power dissipation for efficient operation. 5、Receive immediate fault notification via an alarm output with a normally closed contact.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Power supply module |
| power supply type | Summable | Input voltage | 24 V 20...30 V) DC |
| Input current | 3800 mA | Inrush current | 14 A 20 V<br />25 A 24 V |
| Maximum input power interruption | 100 ms<br />1 ms 20 V | Associated fuse rating | 5 A, slow-blow |
| Output voltage | 5.1 V DC | Power supply output current | 8 A summable |
| Output overvoltage protection | Internal | Output overload protection | Internal |
| Power dissipation | 6 + (1.8 x Iout) where Iout is in A | Alarm output | 1 NC 6 A 220 V power supply fault |
| Local signalling | for power (PWR OK) 1 LED (green) | marking | CE |
| Module format | Standard | Net Weight | 1.43 lb(US) (0.65 kg) |
| Standards | CSA C22.2 No 142<br />UL 508 | Product Certifications | cUL<br />FM Class 1 Division 2 |
| Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice