140CPS22400C

Product ID:31682
Updated: 2026/4/4
schneider 140CPS22400C

Key Features

  • 1Ensure uninterrupted power delivery during primary supply failures. 2、Operate with a wide input voltage range of 19-30Vdc. 3、Protect your system with integrated overcurrent and overvoltage safeguards. 4、Deploy safely in explosive atmospheres and harsh industrial environments. 5、Meet key standards including UL 508, CSA C22.2 No 142, and EU RoHS.
Product Details
140CPS22400C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Power supply module
power supply type
Redundant
Input voltage
24 V 20...30 V) DC
Input current
3800 mA
Inrush current
14 A 20 V<br />25 A 24 V
Maximum input power interruption
100 ms<br />1 ms 20 V
Associated fuse rating
5 A, slow-blow
Output voltage
5.1 V DC
Power supply output current
8 A redundant
Output overvoltage protection
Internal
Output overload protection
2.3 x maximum rated input voltage for 1.3 ms
Power dissipation
6 + (1.8 x Iout) where Iout is in A
Alarm output
1 NC 6 A 220 V power supply fault
Local signalling
for power (PWR OK) 1 LED (green)
marking
CE
Module format
Standard
Net Weight
1.43 lb(US) (0.65 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
UL 508<br />CSA C22.2 No 142
Product Certifications
cUL<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice