140CPS22400C
Product ID:31682
Updated: 2026/4/4

Key Features
- 1Ensure uninterrupted power delivery during primary supply failures. 2、Operate with a wide input voltage range of 19-30Vdc. 3、Protect your system with integrated overcurrent and overvoltage safeguards. 4、Deploy safely in explosive atmospheres and harsh industrial environments. 5、Meet key standards including UL 508, CSA C22.2 No 142, and EU RoHS.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Power supply module |
| power supply type | Redundant | Input voltage | 24 V 20...30 V) DC |
| Input current | 3800 mA | Inrush current | 14 A 20 V<br />25 A 24 V |
| Maximum input power interruption | 100 ms<br />1 ms 20 V | Associated fuse rating | 5 A, slow-blow |
| Output voltage | 5.1 V DC | Power supply output current | 8 A redundant |
| Output overvoltage protection | Internal | Output overload protection | 2.3 x maximum rated input voltage for 1.3 ms |
| Power dissipation | 6 + (1.8 x Iout) where Iout is in A | Alarm output | 1 NC 6 A 220 V power supply fault |
| Local signalling | for power (PWR OK) 1 LED (green) | marking | CE |
| Module format | Standard | Net Weight | 1.43 lb(US) (0.65 kg) |
| Protective treatment | Conformal coating Humiseal 1A33 | Standards | UL 508<br />CSA C22.2 No 142 |
| Product Certifications | cUL<br />FM Class 1 Division 2 | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice