140CPS42400
Product ID:31685
Updated: 2026/4/4

Key Features
- 1Operate with a flexible 48-60V DC input range for various industrial systems. 2、Deliver 8A maximum output in redundant mode for continuous operation. 3、Protect with internal overvoltage and overload safety features. 4、Monitor via alarm output with a 6A 220V NC contact for faults. 5、Signal status with a green PWR OK LED backed by a 2-year warranty.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Power supply module |
| power supply type | Redundant | Input voltage | 48...60 V 48...60 V) DC |
| Input current | 3800 mA | Inrush current | 14 A 40 V |
| Maximum input power interruption | 13 ms 48 V | Associated fuse rating | 2 A, time-lag |
| Output voltage | 5.1 V DC | Power supply output current | 8 A redundant |
| Output overvoltage protection | Internal | Output overload protection | Internal |
| Power dissipation | 17.2 W | Alarm output | 1 NC 6 A 220 V power supply fault |
| Local signalling | for power (PWR OK) 1 LED (green) | marking | CE |
| Module format | Standard | Net Weight | 1.43 lb(US) (0.65 kg) |
| Standards | CSA C22.2 No 142<br />UL 508 | Product Certifications | cUL |
| Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |