  • 1Ensure high reliability and durability for critical industrial applications. 2、Maximize space with a compact design and enhanced power density. 3、Optimize performance using advanced thermal management systems. 4、Meet global safety standards including UL and CE certifications. 5、Deploy in industrial, commercial, and data center environments.
Product Details
140CRP31200C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum
Product or Component Type
Ethernet RIO head for Quantum
Number of port
4
Integrated connection type
Ethernet IP/Modbus TCP service port<br />Ethernet IP/Modbus TCP interlink port<br />Ethernet IP/Modbus TCP device network
communication port protocol
Ethernet IP/Modbus TCP
Communication Service
Diagnostics for remote I/O devices<br />Allows PLC to connect to an Ethernet network<br />RSTP support<br />Configure IP parameters<br />Configuration for remote I/O devices
Topology
Daisy chain loop
Local signalling
for activity 1 LED (green)<br /> for ready 1 LED (green)<br /> for module status (Mod Status) 1 LED (green/red)<br /> for network communication status (Net Status) 1 LED (green/red)
Product Compatibility
140CPU67160<br />140CPU65160<br />140CPU67261<br />140CPU65260<br />140CPU65150
Environmental characteristic
Hazardous location class I division 2 EN/IEC 61131-1<br />Harsh environment
Width
6.6 in (167 mm)
Height
2.0 in (50 mm)
Net Weight
1.221 lb(US) (0.554 kg)
Product Certifications
UL 508<br />C-tick<br />CE
Standards
EN 55011<br />CSA C22.2 No 142<br />IEC 61000-4-16
IP degree of protection
IP20 conforming to EN 61131-2<br />IP20 conforming to IEC 60527
Overvoltage category
Class I EN 61131-2
Ambient air temperature for operation
32…140 °F (0…60 °C) IEC 60068-2-2<br />32…140 °F (0…60 °C) IEC 60068-2-2
Ambient air temperature for storage
-40…185 °F (-40…85 °C) IEC 60068-2-2<br />-40…185 °F (-40…85 °C) IEC 60068-2-2
Vibration resistance
3.5 mm constant amplitude 0.5…8.4 Hz)EN 61131-2<br />1 gn constant acceleration 8.4…150 Hz)EN 61131-2
Operating altitude
6561.68 ft (2000 m)
Maximum altitude transport
9842.5 ft (3000 m)
Relative humidity
93 % conforming to IEC 60068