schneider 140DAI34000C

Key Features

  • 1Handle 16 discrete 24 VAC input channels for comprehensive monitoring. 2、Ensure robust performance within the Modicon Quantum automation family. 3、Operate across a wide 47-63 Hz frequency range for adaptability. 4、Achieve fast response times from 4.9 ms for Off-On transitions. 5、Provide 1780 Vrms electrical isolation for safety and interference protection.
Product Details
140DAI34000C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
Unity Pro<br />Concept<br />ProWORX 32
Discrete input number
16
Group of channels
16
Addressing requirement
1 input word
Discrete input voltage
24 V AC
Input current
12 mA 57...63 Hz<br />10.7 mA 47...53 Hz
Voltage state 1 guaranteed
16...30 V AC 57...63 Hz<br />18...30 V AC 47...53 Hz
Voltage state 0 guaranteed
0...6 V 57...63 Hz<br />0...5 V 47...53 Hz
Input impedance
2600 Ohm capacitive 57...63 Hz<br />3100 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
1.9 mA
Absolute maximum input
30 V continuous<br />32 V 10 s<br />50 V 1 cycle
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between channels
1780 Vrms for 1 minute
Isolation between channels and bus
1780 Vrms for 1 minute
Bus current requirement
180 mA
Maximum power dissipation in W
5.5 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
marking
CE
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
UL 508<br />CSA C22.2 No 142
Product Certifications
FM Class 1 Division 2<br />cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice