140DAI44000C

Product ID:25865
Updated: 2026/4/3
schneider 140DAI44000C

Key Features

  • 1Monitor 16 discrete 48 V AC inputs for high-voltage applications. 2、Integrate seamlessly into standard control system racks. 3、Simplify setup with a single input word addressing requirement. 4、Configure using industry software like Unity Pro and Concept. 5、Enhance system reliability with robust industrial construction.
Product Details
140DAI44000C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
Concept<br />Unity Pro<br />ProWORX 32
Discrete input number
16
Group of channels
16
Addressing requirement
1 input word
Discrete input voltage
48 V AC
Input current
11 mA 57...63 Hz<br />9.3 mA 47...53 Hz
Voltage state 1 guaranteed
34...56 V AC 57...63 Hz<br />36...56 V AC 47...53 Hz
Voltage state 0 guaranteed
0...10 V 57...63 Hz<br />0...10 V 47...53 Hz
Input impedance
5600 Ohm capacitive 57...63 Hz<br />6800 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
1.7 mA
Absolute maximum input
100 V 1 cycle<br />56 V continuous<br />63 V 10 s
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between channels
1780 Vrms for 1 minute
Isolation between channels and bus
1780 Vrms for 1 minute
Bus current requirement
180 mA
Maximum power dissipation in W
5.5 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
marking
CE
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
UL 508<br />CSA C22.2 No 142
Product Certifications
cUL<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice