Key Features

  • 1Monitor 16 discrete input signals with precision.
  • 2Handle 115 V AC inputs for reliable industrial monitoring.
  • 3Ensure safety with leakage current protection and isolation.
  • 4Integrate seamlessly with Concept and Unity Pro software.
  • 5Simplify installation using a standard module format.

Need price and lead time?

Request a quote for original schneider 140DAI54300. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original schneider
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
Unity Pro<br />Concept<br />ProWORX 32
Discrete input number
16
Group of channels
2
Addressing requirement
1 input word
Discrete input voltage
115 V AC
Input current
11.1 mA 57...63 Hz<br />13.2 mA 47...53 Hz
Voltage state 1 guaranteed
79...132 V AC 57...63 Hz<br />85...132 V AC 47...53 Hz
Voltage state 0 guaranteed
0...20 V AC 57...63 Hz<br />0...20 V AC 47...53 Hz
Input impedance
12000 Ohm capacitive 57...63 Hz<br />14400 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
2.1 mA
Absolute maximum input
132 V continuous<br />156 V 10 s<br />200 V 1 cycle
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between group
1780 Vrms for 1 minute
Isolation between group and bus
1780 Vrms for 1 minute
Bus current requirement
180 mA
Maximum power dissipation in W
5.5 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
marking
CE
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
cUL<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice