140DAI55300C

Product ID:25873
Updated: 2026/4/3
schneider 140DAI55300C

Key Features

  • 1Deliver 32 discrete inputs at 115 V AC for reliable data acquisition. 2、Ensure operational safety with robust 1780 Vrms isolation protection. 3、Achieve fast control with a rapid 4.9 ms Off-On response time. 4、Simplify integration using compatibility with Unity Pro software. 5、Reduce energy costs with a low power dissipation of <= 10.9 W.
Product Details
140DAI55300C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
VAC discrete input modules
Software name
Unity Pro<br />ProWORX 32<br />Concept
Discrete input number
32
Group of channels
4
Addressing requirement
2 input words
Discrete input voltage
115 V AC
Input current
11.1 mA 57...63 Hz<br />13.2 mA 47...53 Hz
Voltage state 1 guaranteed
79...132 V AC 57...63 Hz<br />85...132 V AC 47...53 Hz
Voltage state 0 guaranteed
0...20 V AC 57...63 Hz<br />0...20 V AC 47...53 Hz
Input impedance
12000 Ohm capacitive 57...63 Hz<br />14400 Ohm capacitive 47...53 Hz
Network frequency limits
47…63 Hz
Maximum leakage current
2.1 mA
Absolute maximum input
132 V continuous<br />156 V 10 s<br />200 V 1 cycle
Response Time
4.9...0.75 ms x line cycle Off-On<br />7.3...12.3 ms On-Off
Isolation between group
1780 Vrms for 1 minute
Isolation between group and bus
1780 Vrms for 1 minute
Bus current requirement
250 mA
Maximum power dissipation in W
10.9 W
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
marking
CE
Module format
Standard
Net Weight
0.73 lb(US) (0.33 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
cUL<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice