140DAM59000
Product ID:25878
Updated: 2026/4/3

Key Features
- 1Configure 16 discrete inputs and 8 discrete outputs flexibly for efficient signal control. 2、Tolerate input surges up to 200V for one cycle ensuring transient reliability. 3、Protect circuits with RC filters and internal 5A fuses per group. 4、Isolate groups with 1000Vrms and channels with 1780Vrms against faults. 5、Dissipate only 5.5W plus load current for energy-efficient operation.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Mixed discrete I/O module |
| Discrete I/O number | 24 | Discrete input number | 16 2 groups of 8 |
| Addressing requirement | 1 input word<br />0.5 output word | Network frequency limits | 47…63 Hz |
| Discrete input voltage | 115 V AC | input voltage limits | 156 V during 10 s<br />200 V during one cycle<br />132 V typical |
| Voltage state 0 guaranteed | 0...20 V | Voltage state 1 guaranteed | 79...132 V 60 Hz<br />85...132 V 50 Hz |
| Current state 0 guaranteed | <= 0.5 mA | Current state 1 guaranteed | <= 11 mA 50 Hz<br /><= 13.2 mA 60 Hz |
| Input impedance | 14400 Ohm capacitive | Response time | 4.9...0.75 ms at state 0 to state 1<br />7.3...12.3 ms at state 1 to state 0 |
| Discrete output number | 8 2 groups of 4 | Discrete output type | Solid state |
| Discrete output voltage | 115 V | Output voltage limits | 156 V AC during 10 s<br />200 V AC during 1 cycle<br />85...132 V typical AC typical |
| Minimum load | 5 mA | Maximum load current | <= 4 A per point<br /><= 8 A per group<br /><= 8 A per module |
| Maximum voltage drop | <1.5 V | Absolute maximum output | 20 A 2 cycles per point<br />26 A 3 cycles per group<br />30 A 1 cycle per point<br />30 A 2 cycles per group<br />45 A 1 cycle per group<br />10 A 3 cycles per point |
| DV/dt | 400 V/µs | Maximum leakage current | 2.1 mA 115 V AC input circuit<br />2 mA output circuit |
| Response time on output | <= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0 | Protection Type | On output by RC filter<br />Internal output protection by 5 A fuse per group |
| Isolation between group | 1000 Vrms for 1 minute | Isolation between channels and bus | 1780 Vrms for 1 minute |
| Fault indication | Loss of field power on output<br />Blown fuse on output | Power dissipation | 5.5 W + (1.1 x total module load current) |
| External power requirement | 85...132 V AC for output circuit | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for no voltage in output and input (F) 1 LED (red)<br /> for output is turned on 2 LEDs (green)<br /> for fault detected on the input point 2 LEDs (red)<br /> for fault detected on the output point 2 LEDs (red) |
| marking | CE | Bus current requirement | 250 mA |
| Net Weight | 0.99 lb(US) (0.45 kg) | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) | Standards | FM Class 1 Division 2<br />UL 508<br />CSA C22.2 No 142 |
| Product Certifications | cUL |
Specifications may be subject to change without notice