140DAO84000
Product ID:25880
Updated: 2026/4/3

Key Features
- 1Control 16 isolated outputs independently for flexible automation. 2、Handle 400 Vrms surge spikes to protect against voltage transients. 3、Minimize voltage drop to 1.5V for efficient and stable operation. 4、Monitor status with 16 green LEDs and one red fault indicator. 5、Operate within a 47-63 Hz range supporting 20-253 V AC outputs.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | AC discrete output modules |
| Discrete output number | 16 | Discrete output type | Isolated |
| Group of channels | 16 groups of 1 channel | Supply frequency | 47...63 Hz |
| Maximum voltage drop | 1.5 V | Discrete output voltage | 20...253 V AC |
| Addressing requirement | 1 output word | Absolute maximum output | 300 Vrms 10 s AC<br />400 Vrms 1 cycle AC |
| Maximum load current | 1 mA rms 24 Vrms off state leakage per output<br />1 mA rms 48 Vrms off state leakage per output<br />2 mA rms 115 Vrms off state leakage per output<br />2.5 mA rms 230 Vrms off state leakage per output<br />3 A rms 200...230 V per output<br />4 A rms 24...115 V per output<br />16 A rms per module<br />4 A rms sum of four points, continuous | Surge current | 10 A during 3 cycles per point<br />20 A during 2 cycles per point<br />30 A during 1 cycle per point |
| DV/dt | 400 V/ms | Response Time | <= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0 |
| Protection Type | Internal by RC filter | Power dissipation | 1.85 + (1.1 V x total module load current) |
| Associated fuse rating | 5 A | marking | CE |
| Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green) | Bus current requirement | 350 mA |
| Module format | Standard | Net Weight | 1.069 lb(US) (0.485 kg) |
| Product Certifications | cUL<br />FM Class 1 Division 2 | Standards | UL 508<br />CSA C22.2 No 142 |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 4 kV (contact discharge) conforming to IEC 801-2<br />Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 801-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice