  • 1Control 16 discrete AC output channels precisely. 2、Protect systems with robust internal RC filters and 5-amp fuses. 3、Operate across a wide 83-253 V AC voltage range. 4、Reduce energy costs through low power dissipation design. 5、Ensure reliability in high-availability industrial automation setups.
Product Details
140DAO84210
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
AC discrete output modules
Discrete output number
16
Group of channels
4 groups of 4 channels
Supply frequency
47...63 Hz
Maximum voltage drop
1.5 V
Discrete output voltage
83...253 V AC
Addressing requirement
1 output word
Absolute maximum output
300 Vrms 10 s AC<br />400 Vrms 1 cycle AC
Maximum load current
2 mA rms 115 Vrms off state leakage per output<br />2.5 mA rms 230 Vrms off state leakage per output<br />3 A rms 170...253 V per output<br />4 A rms 85...132 V per output<br />16 A rms per module<br />4 A rms per group
Surge current
10 A during 3 cycles per point<br />20 A during 2 cycles per point<br />30 A during 1 cycle per point<br />25 A during 3 cycles per group<br />30 A during 2 cycles per group<br />45 A during 1 cycle per group
DV/dt
400 V/ms
Response Time
<= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0
Fault indication
Blown fuse<br />Loss of field power
Protection Type
Internal by RC filter<br />Internal output protection by 5 A fuse
Power dissipation
1.85 + (1.1 V x total module load current)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
Bus current requirement
350 mA
Module format
Standard
Net Weight
0.99 lb(US) (0.45 kg)
Product Certifications
cUL<br />FM Class 1 Division 2
Standards
UL 508<br />CSA C22.2 No 142
Electromagnetic compatibility
Electrostatic discharge immunity test - test level: 4 kV (contact discharge) conforming to IEC 801-2<br />Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 801-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)