Key Features
- 1Deliver precise control with a fast ≤0.5 ms response time. 2、Ensure reliable operation using robust surge protection mechanisms. 3、Minimize energy consumption through efficient power dissipation design. 4、Simplify setup and configuration with single output word addressing. 5、Achieve robust performance in demanding industrial automation environments.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | AC discrete output modules |
| Discrete output number | 16 | Group of channels | 4 groups of 4 channels |
| Supply frequency | 47...63 Hz | Maximum voltage drop | 1.5 V |
| Discrete output voltage | 20...56 V AC | Addressing requirement | 1 output word |
| Absolute maximum output | 100 Vrms 1 cycle AC<br />63 Vrms 10 s AC<br />111 Vrms 1.3 s AC | Maximum load current | 16 A rms per module<br />4 A rms per group<br />4 A rms 20...56 V per output |
| Surge current | 45 A during 1 cycle per group<br />25 A during 2 cycles per group<br />30 A during 3 cycles per group | DV/dt | 400 V/ms |
| Response Time | <= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0 | Fault indication | Blown fuse<br />Loss of field power |
| Protection Type | Internal by RC filter<br />Internal output protection by 5 A fuse | Power dissipation | 1.85 + (1.1 V x total module load current) |
| marking | CE | Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green) |
| Bus current requirement | 350 mA | Module format | Standard |
| Net Weight | 0.99 lb(US) (0.45 kg) | Product Certifications | FM Class 1 Division 2<br />cUL |
| Standards | UL 508<br />CSA C22.2 No 142 | Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 4 kV (contact discharge) conforming to IEC 801-2<br />Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 801-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 801-3 |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Relative Humidity | 95 % without condensation | Operating altitude | <= 16404.2 ft (5000 m) |