Key Features

  • 1Control 32 discrete output channels in four groups.
  • 2Operate across a versatile 20-253V AC voltage range.
  • 3Safeguard circuits with internal 4A fuse and RC filter.
  • 4Achieve swift state transitions under 0.5ms response time.
  • 5Deliver robust performance up to 1A RMS per output.

Need price and lead time?

Request a quote for original schneider 140DAO85300. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original schneider
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
AC discrete output modules
Discrete output number
32
Group of channels
4 groups of 8 channels
Supply frequency
47...63 Hz
Maximum voltage drop
1.5 V
Discrete output voltage
20...253 V AC
Addressing requirement
2 output words
Absolute maximum output
300 Vrms 10 s AC<br />400 Vrms 1 cycle AC
Maximum load current
16 A rms per module<br />4 A rms per group<br />0.88 mA 230 V off state leakage per output<br />1 A rms 20...253 V per output
Surge current
2.5 A 1 ms
DV/dt
400 V/ms
Response Time
<= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0
Protection Type
Internal output protection by 4 A fuse<br />Internal by RC filter
Power dissipation
1.60 + (1.0 V x total module load current)
Marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
Bus current requirement
320 mA
Module format
Standard
Net Weight
0.99 lb(US) (0.45 kg)
Product Certifications
cUL<br />FM Class 1 Division 2
Standards
CSA C22.2 No 142<br />UL 508
Electromagnetic compatibility
Electrostatic discharge immunity test - test level: 4 kV (contact discharge) conforming to IEC 801-2<br />Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 801-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)