- 1Control 32 discrete output channels in four groups. 2、Operate across a versatile 20-253V AC voltage range. 3、Safeguard circuits with internal 4A fuse and RC filter. 4、Achieve swift state transitions under 0.5ms response time. 5、Deliver robust performance up to 1A RMS per output.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | AC discrete output modules |
| Discrete output number | 32 | Group of channels | 4 groups of 8 channels |
| Supply frequency | 47...63 Hz | Maximum voltage drop | 1.5 V |
| Discrete output voltage | 20...253 V AC | Addressing requirement | 2 output words |
| Absolute maximum output | 300 Vrms 10 s AC<br />400 Vrms 1 cycle AC | Maximum load current | 16 A rms per module<br />4 A rms per group<br />0.88 mA 230 V off state leakage per output<br />1 A rms 20...253 V per output |
| Surge current | 2.5 A 1 ms | DV/dt | 400 V/ms |
| Response Time | <= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0 | Protection Type | Internal output protection by 4 A fuse<br />Internal by RC filter |
| Power dissipation | 1.60 + (1.0 V x total module load current) | Marking | CE |
| Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) | Bus current requirement | 320 mA |
| Module format | Standard | Net Weight | 0.99 lb(US) (0.45 kg) |
| Product Certifications | cUL<br />FM Class 1 Division 2 | Standards | CSA C22.2 No 142<br />UL 508 |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 4 kV (contact discharge) conforming to IEC 801-2<br />Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 801-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice