140DAO85300
Product ID:25888
Updated: 2026/7/14

Key Features
- 1Control 32 discrete output channels in four groups.
- 2Operate across a versatile 20-253V AC voltage range.
- 3Safeguard circuits with internal 4A fuse and RC filter.
- 4Achieve swift state transitions under 0.5ms response time.
- 5Deliver robust performance up to 1A RMS per output.
Need a quote? Enter your quantity and get pricing fast.
Qty
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | AC discrete output modules |
| Discrete output number | 32 | Group of channels | 4 groups of 8 channels |
| Supply frequency | 47...63 Hz | Maximum voltage drop | 1.5 V |
| Discrete output voltage | 20...253 V AC | Addressing requirement | 2 output words |
| Absolute maximum output | 300 Vrms 10 s AC<br />400 Vrms 1 cycle AC | Maximum load current | 16 A rms per module<br />4 A rms per group<br />0.88 mA 230 V off state leakage per output<br />1 A rms 20...253 V per output |
| Surge current | 2.5 A 1 ms | DV/dt | 400 V/ms |
| Response Time | <= 0.5 ms at state 0 to state 1<br /><= 0.5 ms at state 1 to state 0 | Protection Type | Internal output protection by 4 A fuse<br />Internal by RC filter |
| Power dissipation | 1.60 + (1.0 V x total module load current) | Marking | CE |
| Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) | Bus current requirement | 320 mA |
| Module format | Standard | Net Weight | 0.99 lb(US) (0.45 kg) |
| Product Certifications | cUL<br />FM Class 1 Division 2 | Standards | CSA C22.2 No 142<br />UL 508 |
| Electromagnetic compatibility | Electrostatic discharge immunity test - test level: 4 kV (contact discharge) conforming to IEC 801-2<br />Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 801-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice