140DDI35300
Product ID:25892
Updated: 2026/4/3

Key Features
- 1Maximize uptime with 32 discrete input channels for comprehensive signal management. 2、Ensure real-time control with a fast ≤1 ms response time for state transitions. 3、Protect your system using advanced electrical isolation and fuse cutouts. 4、Simplify monitoring and diagnostics via a convenient LED status display. 5、Achieve reliable performance in demanding industrial automation environments.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | Low voltage dc discrete input modules |
| Discrete input number | 32 | Group of channels | 4 |
| Logic input | Positive (sink) | Discrete input voltage | 24 V DC |
| input voltage limits | 19.2...30 V | Voltage state 1 guaranteed | 15...30 V DC |
| Voltage state 0 guaranteed | -3...5 V DC | Current state 1 guaranteed | >= 2 mA at Us = 5.5 V and Uin = 0 V |
| Current state 0 guaranteed | <= 0.5 mA | Addressing requirement | 2 input words |
| input impedance | 2500 Ohm | Maximum leakage current | 200 mA at Us = 5.5 V and Uin = 4 V |
| Absolute maximum input | 30 V continuous<br />56 V during 1.3 ms decaying pulse | Response Time | <= 1 ms from state 0 to state 1<br /><= 1 ms from state 1 to state 0 |
| Protection Type | Input protection by resistor limited | Power dissipation | 1.7 W + (0.36 x number of points on) |
| Isolation between group and bus | 1780 Vrms for 1 minute | Isolation between group | 500 Vrms for 1 minute |
| Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) | marking | CE |
| Bus current requirement | 330 mA | Module format | Standard |
| Net Weight | 0.7 lb(US) (0.3 kg) | Standards | CSA C22.2 No 142<br />UL 508 |
| Product Certifications | C-tick<br />DNV<br />RINA<br />RMRS<br />BV<br />GOST<br />ABS | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
Specifications may be subject to change without notice