Key Features

  • 1Organize 96 discrete input points into 6 channel groups for efficient processing.
  • 2Utilize positive (sink) logic for accurate input detection and reduced noise.
  • 3Achieve rapid state transitions in ≤3 ms for real-time monitoring.
  • 4Optimize power management with 1.35 W base plus 0.13 W per active point.
  • 5Ensure protection with 500 VRMS isolation for up to one minute.

Need price and lead time?

Request a quote for original schneider 140DDI36400C. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original schneider
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Low voltage dc discrete input modules
Discrete input number
96
Group of channels
6
Logic input
Positive (sink)
Discrete input voltage
24 V DC
input voltage limits
19.2...30 V
Voltage state 1 guaranteed
15...30 V DC
Voltage state 0 guaranteed
5 V DC
Current state 1 guaranteed
>= 2.5 mA
Current state 0 guaranteed
>= 0.7 mA
Addressing requirement
6 words
input impedance
6700 Ohm
Absolute maximum input
30 V continuous<br />50 V decaying pulse
Response Time
<= 2 ms from state 0 to state 1<br /><= 3 ms from state 1 to state 0
Power dissipation
1.35 W + (0.13 x number of points on)
Isolation between group
500 Vrms for 1 minute
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 96 LEDs (green)
marking
CE
Bus current requirement
270 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142<br />UL 508
Product Certifications
C-tick<br />FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)