140DDI84100

Product ID:28945
Updated: 2026/7/14
schneider 140DDI84100

Key Features

  • 1Feature 16 distinct inputs grouped into eight channels.
  • 2Handle input voltages from 10 to 60 volts DC.
  • 3Offer a fast 4 ms response time for transitions.
  • 4Provide high isolation of 700 Vrms between groups.
  • 5Deliver a compact design weighing only 0.3 kg.

Need price and lead time?

Request a quote for original schneider 140DDI84100. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original schneider
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete input modules
Discrete input number
16
Group of channels
8
Logic input
Positive (sink)
input voltage limits
10...60 V
Input voltage
12 V 5…10 mA DC<br />24 V 6…30 mA DC<br />48 V 2…15 mA DC<br />60 V 1…5 mA DC
Voltage state 1 guaranteed
11...24 V 24 V +/- 20 %<br />34...48 V 48 V +/- 20 %<br />45...60 V 60 V +/- 20 %<br />9...12 V 12 V +/- 5 %
Voltage state 0 guaranteed
0...1.8 V 12 V +/- 5 %<br />0...10 V 48 V +/- 20 %<br />0...5 V 24 V +/- 20 %<br />0...9 V 60 V +/- 20 %
Absolute maximum voltage
75 V
Addressing requirement
1 input word
Response Time
4 ms from state 0 to state 1<br />4 ms from state 1 to state 0
Switching frequency
<= 100 Hz
Isolation between group and bus
2500 Vrms DC for 1 minute
Isolation between group
700 Vrms DC for 1 minute
Power dissipation
1 W + (0.62 x number of points on)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 16 LEDs (green)
Bus current requirement
200 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Standards
UL 508<br />CSA C22.2 No 142
Product Certifications
FM Class 1 Division 2<br />C-tick
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice

Still deciding on 140DDI84100?

Our engineers can confirm stock, price, and lead time for this schneider part.

Get a no-obligation quote in 1 minute.

Chat with us