Key Features

  • 1Process signals efficiently with 32 discrete inputs across four groups. 2、Ensure reliable operation with 2500 Vrms robust isolation against interference. 3、Achieve rapid 4 ms response for applications needing quick input processing. 4、Reduce system strain via efficient power dissipation design. 5、Collect precise data for material handling and packaging machines.
Product Details
140DDI85300
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete input modules
Discrete input number
32
Group of channels
4
Logic input
Positive (sink)
input voltage limits
10...60 V
Input voltage
12 V 5…10 mA DC<br />24 V 6…30 mA DC<br />48 V 2…15 mA DC<br />60 V 1…5 mA DC
Voltage state 1 guaranteed
9...12 V 12 V +/- 5 %<br />11...24 V 24 V - 15...20 %<br />34...48 V 48 V - 15...20 %<br />45...60 V 60 V - 15...20 %
Voltage state 0 guaranteed
0...1.8 V 12 V +/- 5 %<br />0...10 V 48 V - 15...20 %<br />0...12.5 V 60 V - 15...20 %<br />0...5 V 24 V - 15...20 %
Absolute maximum voltage
75 V
Addressing requirement
2 input words
Response Time
4 ms from state 0 to state 1<br />4 ms from state 1 to state 0
Switching frequency
<= 100 Hz
Isolation between group and bus
2500 Vrms DC for 1 minute
Isolation between group
700 Vrms DC for 1 minute
Power dissipation
1 W + (0.25 x number of points on)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for input status 32 LEDs (green)
Bus current requirement
300 mA
Module format
Standard
Net Weight
0.650 lb(US) (0.295 kg)
Standards
EN/IEC 61131-2<br />CSA C22.2 No 142<br />UL 508
Product Certifications
RCM<br />Merchant Navy<br />UL<br />EAC<br />CSA<br />CE<br />hazardous location class 1, division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice