140DDM69000C

Product ID:28952
Updated: 2026/4/3
schneider 140DDM69000C

Key Features

  • 1Handle up to 156.2 V DC with minimal current draw. 2、Process mixed signals with 4 discrete inputs and 4 outputs. 3、Protect circuits with transient suppression and 5A fuses. 4、Ensure safety via 1780 Vrms I/O isolation. 5、Monitor status easily with multiple LED indicators.
Product Details
140DDM69000C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Mixed discrete I/O module
Discrete I/O number
8
Discrete input number
4 1 group of 8
Discrete input logic
Sink
Addressing requirement
1 output word<br />1 input word
Network frequency limits
47…63 Hz
Discrete input voltage
125 V DC
input voltage limits
156.2 V including ripple
Voltage state 0 guaranteed
0...36 V
Voltage state 1 guaranteed
88...156.2 V
Current state 0 guaranteed
<= 1.2 mA
Current state 1 guaranteed
>= 2 mA
Response time
0.5 or 1.5 ms depending on the filter at state 0 to state 1<br />0.5 or 1.5 ms depending on the filter at state 1 to state 0
Discrete output number
4 1 group of 4
Discrete output type
Solid state, isolated
Discrete output logic
Source or sink
Discrete output voltage
24...125 V
Output voltage limits
19.2...156.2 V DC typical
Maximum load current
<= 16 A per module<br /><= 4 A per point
Maximum voltage drop
<0.75 V 4 A
Absolute maximum output
30 A during 500 ms per point
Maximum load capacitance
0.1 µF 150 V DC<br />0.6 µF 24 V DC
Maximum leakage current
1.2 mA 150 V DC
Protection Type
On input by resistor limited<br />On output by transient voltage suppression<br />Internal output protection by 5 A fuse per group
Associated fuse rating
5 A
Isolation between group of I/O channels
1780 Vrms for 1 minute
Isolation between group and bus
2500 Vrms for 1 minute
Isolation between channels
1780 Vrms for 1 minute
Fault indication
Overcurrent on output
Power dissipation
0.4 W + (1 x input point on) + (0.75 total output load current)
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for no voltage in output and input (F) 1 LED (red)<br /> for fault detected on the output point 2 LEDs (red)<br /> for output is turned on 4 LEDs (green)<br /> for fault detected on the input point 4 LEDs (red)
marking
CE
Bus current requirement
350 mA
Net Weight
0.7 lb(US) (0.3 kg)
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)
Protective treatment
Conformal coating Humiseal 1A33
Standards
FM Class 1 Division 2<br />UL 508<br />CSA C22.2 No 142
Product Certifications
cUL

Specifications may be subject to change without notice