Key Features
- 1Achieve high-speed switching in ≤250 microseconds for rapid digital signaling. 2、Ensure precise 5V DC control with a low voltage state ≤0.2V. 3、Protect against surges with built-in transient voltage suppression and fuses. 4、Optimize energy efficiency with 4W power dissipation and 2800 mA consumption. 5、Monitor status in real-time via green LEDs for bus and output conditions.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Modicon Quantum automation platform | Product or Component Type | TTL discrete output module |
| Discrete output number | 32 | Group of channels | 4 groups of 8 channels |
| Discrete output type | Positive (sink)<br />TTL | Addressing requirement | 2 output words |
| Discrete output voltage | 5 V DC | Voltage state 1 guaranteed | <= 0.2 V |
| [Us] rated supply voltage | 4...5.5 V DC | Absolute maximum output | 15 V 0.0013 s decaying voltage pulse DC |
| Internal pullup resistor | 440 Ohm | Maximum load current | <= 2.4 A per module<br /><= 600 mA each group<br /><= 75 mA each point |
| Surge current | 750 A 0.5 ms between each point | Response time | <= 250 µs at state 0 to state 1 resistive<br /><= 250 µs at state 1 to state 0 resistive |
| Protection Type | Output protection by transient voltage suppression<br />Internal by fuse | Fault indication | Loss of field power<br />Blown fuse |
| Power dissipation | 4 W | Maximum supply current | 0.4 A |
| Isolation between group | 500 Vrms for 1 minute | marking | CE |
| Local signalling | for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green) | Bus current requirement | 350 mA |
| Current consumption | 2800 mA 5 V DC | Module format | Standard |
| Net Weight | 0.99 lb(US) (0.45 kg) | Product Certifications | RMRS<br />GOST<br />C-tick<br />FM Class 1 Division 2 |
| Standards | UL 508<br />CSA C22.2 No 142 | Resistance to electrostatic discharge | 4 kV contact IEC 801-2<br />8 kV on air IEC 801-2 |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3 | Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |