140DDO15310C

Product ID:28954
Updated: 2026/4/3
schneider 140DDO15310C

Key Features

  • 1Control 32 TTL discrete outputs for versatile device operation. 2、Operate reliably with 5V DC voltage for stable performance. 3、Receive a comprehensive 2-year warranty from Schneider Electric. 4、Achieve ≤250 μs response time for fast-paced applications. 5、Ensure protection with internal fuse and transient suppression.
Product Details
140DDO15310C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
TTL discrete output module
Discrete output number
32
Group of channels
4 groups of 8 channels
Discrete output type
TTL<br />Positive (sink)
Addressing requirement
2 output words
Discrete output voltage
5 V DC
Voltage state 1 guaranteed
<= 0.2 V
[Us] rated supply voltage
4...5.5 V DC
Absolute maximum output
15 V 0.0013 s decaying voltage pulse DC
Internal pullup resistor
440 Ohm
Maximum load current
<= 2.4 A per module<br /><= 600 mA each group<br /><= 75 mA each point
Surge current
750 A 0.5 ms between each point
Response time
<= 250 µs at state 0 to state 1 resistive<br /><= 250 µs at state 1 to state 0 resistive
Protection Type
Output protection by transient voltage suppression<br />Internal by fuse
Fault indication
Blown fuse<br />Loss of field power
Power dissipation
4 W
Maximum supply current
0.4 A
Isolation between group
500 Vrms for 1 minute
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
Bus current requirement
350 mA
Current consumption
2800 mA 5 V DC
Module format
Standard
Net Weight
0.99 lb(US) (0.45 kg)
Protective treatment
Conformal coating Humiseal 1A33
Product Certifications
FM Class 1 Division 2<br />C-tick<br />RMRS<br />GOST
Standards
CSA C22.2 No 142<br />UL 508
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice