140DDO35310C

Product ID:28960
Updated: 2026/4/3
schneider 140DDO35310C

Key Features

  • 1Control 32 discrete DC outputs in a high-density design. 2、Ensure robust protection with 1780 Vrms isolation. 3、Achieve fast switching with a 1 ms response time. 4、Protect circuits with internal 3A and 5A fuses. 5、Maintain efficiency with low leakage current.
Product Details
140DDO35310C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete output module
Discrete output number
32
Group of channels
4 groups of 8
Discrete output logic
Negative logic (sink)
Addressing requirement
2 output words
Discrete output voltage
24 V DC
Output voltage limits
19.2...30 V
Absolute maximum output
50 V 1 s decaying pulse
Maximum voltage drop
<0.4 V 0.5 A
Maximum load current
16 A per module<br />4 A per group
Surge current
5 A 1 ms
Response Time
<= 1 ms at state 0 to state 1<br /><= 1 ms at state 1 to state 0
Maximum leakage current
0.4 mA 30 V
Load inductance
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))
Maximum tungsten load
12 W 24 V
Fault indication
Loss of field power<br />Blown fuse
Associated fuse rating
3 A each point<br />5 A per group
Isolation between channels and bus
1780 Vrms DC for 1 minute
Isolation between group
500 Vrms DC for 1 minute
Protection Type
Internal output protection by 5 A fuse per group
Power dissipation
2.0 W + (0.4 V x total load current)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green)<br /> for external fault detected (F) 1 LED (red)<br /> for input status 32 LEDs (green)
Bus current requirement
330 mA
Module format
Standard
Net Weight
0.99 lb(US) (0.45 kg)
Protective treatment
Conformal coating Humiseal 1A33
Product Certifications
RMRS<br />GOST<br />C-tick<br />RINA<br />FM Class 1 Division 2
Standards
CSA C22.2 No 142<br />UL 508
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80…2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice