140DII33000C

Product ID:28968
Updated: 2026/4/3
schneider 140DII33000C

Key Features

  • 1Ensure safe operation in hazardous areas with intrinsic safety design. 2、Acquire reliable data from 8 discrete digital input points. 3、Maximize uptime with high-reliability design for harsh environments. 4、Meet strict standards including ATEX, IECEx, and CSA for global compliance. 5、Secure your investment with a 2-year Schneider Electric warranty.
Product Details
140DII33000C
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon Quantum automation platform
Product or Component Type
Intrinsically safe discrete input module
Software Designation
ProWORX<br />Unity Pro<br />Concept
Software Version
V2.2 and above
Product destination
In conjunction with products for zone 20, 21 or 22
Discrete input number
8
No load voltage
8 V
Short-circuit current
8 mA
Switching hysteresis
0.2 mA
Current state 0 guaranteed
<= 1.2 mA
Current state 1 guaranteed
>= 2.1 mA
Switching frequency
100 Hz
Response time
1 ms resistive at state 0 to state 1<br />1 ms resistive at state 1 to state 0
Internal resistance
2.5 kOhm
Protection Type
Internal by fuse<br />Resistor limited
Isolation between channels and bus
2500 V for 1 minute DC<br />1780 V 47...63 Hz AC
Fault type
Resistor limited
Hot swapping fallback
Not allowed per intrinsic safety standards
Power dissipation in W
2 W
marking
CE<br />II1 G/D-EEx ia IIC
Bus current requirement
0.4 A
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
UL 508<br />EN 50020<br />EN 50014<br />EN 50039<br />EN 50281-1-1<br />CSA C22.2 No 142<br />Directive ATEX 94/9/EC<br />EN 50284
Dust zone
Outside zone
Product Certifications
FM Class 1 Division 2
Resistance to electrostatic discharge
4 kV contact IEC 801-2<br />8 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80...1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)

Specifications may be subject to change without notice