ATS48D22Y
Product ID:31289
Updated: 2026/4/5

Key Features
- 1Prevent motor restarts during excessive temperature rise. 2、Configure high starting torque and lower ending torque for gradual loading. 3、Integrate PTC probes for motor and analog probes for starter thermal protection. 4、Suit constant and variable torque applications like centrifugal pumps. 5、Meet international standards including EN/IEC 60947-4-2, CSA, and UL.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Altistart 48 | Product or Component Type | Soft starter |
| Product destination | Asynchronous motors | Product Specific Application | Heavy duty industry and pumps |
| Device short name | ATS48 | Utilisation category | AC-53A |
| Ue power supply voltage | 208...690 V - 15...10 % | power supply frequency | 50...60 Hz - 5...5 % |
| Motor power kW | 11 kW 400 V for standard applications<br />11 kW 440 V for standard applications<br />11 kW 500 V for standard applications<br />11 kW 525 V for standard applications<br />11 kW 660 V for severe applications<br />15 kW 660 V for standard applications<br />15 kW 690 V for severe applications<br />4 kW 230 V for severe applications<br />9 kW 500 V for severe applications<br />9 kW 525 V for severe applications<br />7.5 kW 400 V for severe applications<br />7.5 kW 440 V for severe applications<br />18.5 kW 690 V for standard applications<br />5.5 kW 230 V for standard applications | Maximum Horse Power Rating | 10 hp 460 V for severe applications<br />15 hp 460 V for standard applications<br />15 hp 575 V for severe applications<br />20 hp 575 V for standard applications<br />3 hp 208 V for severe applications<br />5 hp 208 V for standard applications<br />5 hp 230 V for severe applications<br />7.5 hp 230 V for standard applications |
| Device connection | In the motor supply line | Protection type | Phase failure line<br />Thermal protection motor<br />Thermal protection starter |
| Standards | EN/IEC 60947-4-2 | Product Certifications | CSA<br />SEPRO<br />UL<br />GOST<br />NOM 117<br />TCF<br />CCC<br />C-tick<br />DNV |
| marking | CE | Discrete input number | 5 |
| Discrete input type | PTC, 750 Ohm 77 °F (25 °C)<br />Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm | Discrete input logic | Positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA |
| Minimum switching current | 10 mA 6 V DC relay outputs | Discrete output number | 2 |
| Discrete output type | LO1) logic output 0 V common configurable<br />LO2) logic output 0 V common configurable<br />R1) relay outputs fault relay NO<br />R2) relay outputs end of starting relay NO<br />R3) relay outputs motor powered NO | Analogue output type | Current output AO 0-20 mA or 4-20 mA 500 Ohm |
| communication port protocol | Modbus | Connector Type | 1 RJ45 |
| Communication data link | Serial | Physical interface | RS485 multidrop |
| Transmission Rate | 4800, 9600 or 19200 bps | Function Available | External bypass (optional) |
| Operating position | Vertical +/- 10 degree | Height | 10.8 in (275 mm) |
| Width | 6.3 in (160 mm) | Depth | 7.5 in (190 mm) |
| Net Weight | 10.8 lb(US) (4.9 kg) | Electromagnetic compatibility | Conducted and radiated emissions level A IEC 60947-4-2<br />Conducted and radiated emissions level B IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5 |
| Relative humidity | 0…95 % without condensation or dripping water EN/IEC 60068-2-3 | Ambient air temperature for operation | 104…140 °F (40…60 °C) with current derating of 2 % per °C)<br />14…104 °F (-10…40 °C) without derating) |
| Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) | Operating altitude | <= 3280.84 ft (1000 m) without derating<br />> 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m |
Specifications may be subject to change without notice