Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Altistart U01 and TeSys U
Product or Component Type
Soft starter
Product destination
Asynchronous motors
Product Specific Application
Simple machine
Device short name
ATSU01
Phase
3 phase
[Us] rated supply voltage
200...480 V - 10...10 %
Motor power kW
11 kW, 3 phase 400 V<br />4 kW, 3 phase 230 V<br />7.5 kW, 3 phase 400 V<br />5.5 kW, 3 phase 230 V
Maximum Horse Power Rating
5 hp, 3 phase 230 V<br />7.5 hp, 3 phase 230 V<br />10 hp, 3 phase 460 V<br />15 hp, 3 phase 460 V
IcL starter rating
22 A
Utilisation category
AC-53B EN/IEC 60947-4-2
Current consumption
100 mA
Type of start
Start with voltage ramp
Power dissipation in W
2.5 W at full load and at end of starting<br />222.5 W in transient state
Assembly style
With heat sink
Function Available
Integrated bypass
Supply voltage limits
180…528 V
Supply frequency
50...60 Hz - 5...5 %
Network Frequency
47.5...63 Hz
Output voltage
<= power supply voltage
[Uc] control circuit voltage
24 V DC +/- 10 %
Starting time
1 s / 100<br />5 s / 20<br />10 s / 10<br />Adjustable from 1 to 10 s
Deceleration time symb
Adjustable from 1 to 10 s
Starting torque
30...80 % of starting torque of motor connected directly on the line supply
Discrete input type
Logic LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
Discrete input voltage
24...40 V
Input output isolation
Galvanic between power and control
Discrete input logic
Positive LI1, LI2, BOOST < 5 V <= 0.2 mA > 13 V, >= 0.5 mA
Discrete output current
2 A DC-13<br />3 A AC-15
Discrete output type
Open collector logic LO1 end of starting signal<br />Relay outputs R1A, R1C NO
Discrete output voltage
24 V 6...30 V) open collector logic
Minimum switching current
10 mA 6 V DC relay outputs
Maximum switching current
Relay outputs 2 A 30 V DC cos phi = 0.5 20 ms inductive<br />Relay outputs 2 A 250 V AC AC-15 cos phi = 0.5 20 ms inductive
Maximum switching voltage
440 V relay outputs
Display type
1 LED Green)starter powered up<br />1 LED Yellow)nominal voltage reached
Tightening torque
16.8…22.1 lbf.in (1.9…2.5 N.m)<br />4.4 lbf.in (0.5 N.m)
Electrical connection
4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit<br />Screw connector - rigid without cable end 1 0.5...2.5 mm² AWG 14 control circuit<br />4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit<br />Screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit<br />Screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit<br />4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit<br />Screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit<br />4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit<br />4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit<br />Screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
marking
CE
Operating position
Vertical +/- 10 degree
Height
12.4 in (314 mm)
Width
1.8 in (45 mm)
Depth
6.7 in (170 mm)
Net Weight
1.08 lb(US) (0.49 kg)
Motor power range AC-3
4…6 kW 200…240 V 3 phase<br />7…11 kW 380…440 V 3 phase
Motor starter type
Soft starter
Electromagnetic compatibility
Conducted and radiated emissions level B CISPR 11<br />Conducted and radiated emissions level B IEC 60947-4-2<br />Damped oscillating waves level 3 IEC 61000-4-12<br />Electrostatic discharge level 3 IEC 61000-4-2<br />EMC immunity EN 50082-1<br />EMC immunity level B EN 50082-2<br />Harmonics level 3 IEC 1000-3-2<br />Harmonics level 3 IEC 1000-3-4<br />Immunity to electrical transients level 4 IEC 61000-4-4<br />Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3<br />Voltage/current impulse level 3 IEC 61000-4-5<br />Conducted and radiated emissions level 3 IEC 61000-4-6<br />Immunity to conducted interference caused by radio-electrical fields level 4 IEC 61000-4-11
Standards
EN/IEC 60947-4-2
Product Certifications
C-tick<br />CSA<br />UL<br />CCC
IP Degree of Protection
IP20
Pollution degree
2 EN/IEC 60947-4-2
Vibration resistance
1 gn 13…150 Hz)EN/IEC 60068-2-6<br />1.5 mm peak to peak 3…13 Hz)EN/IEC 60068-2-6
Shock resistance
15 gn 11 ms EN/IEC 60068-2-27
Relative humidity
5…95 % without condensation or dripping water EN/IEC 60068-2-3
Ambient air temperature for operation
14…104 °F (-10…40 °C) without derating)<br />104…122 °F (40…50 °C) with current derating of 2 % per °C)
Ambient air temperature for storage
-13…158 °F (-25…70 °C) EN/IEC 60947-4-2
Operating altitude
<= 3280.84 ft (1000 m) without derating<br />> 3280.84 ft (1000 m) with current derating of 2.2 % per additional 100 m