ATV6000D650A2424ND
Product ID:23672
Updated: 2026/4/3

Key Features
- 1Deliver 697 horsepower for heavy-duty industrial applications. 2、Ensure safety and compliance with UL certification. 3、Operate at 2.4 kV for precise medium voltage control. 4、Optimize energy and asset management with smart connectivity. 5、Maximize uptime with reliable, continuous operation design.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Altivar Process ATV6000 | Product or Component Type | Medium voltage variable speed drive |
| Device short name | ATV6000 | Product Specific Application | Process and utilities |
| Assembly style | In floor-standing enclosure | Provided Equipment | Cooling fans<br />Human machine interface<br />Plinth<br />Medium voltage arrestors<br />Power cells<br />Enclosure<br />Phase-shifting transformer |
| Colour of enclosure | Light grey RAL 7035) | IP degree of protection | IP31 conforming to IEC 60529 |
| Type of cooling | Forced convection | input type | 54 pulse diode rectifier bridge |
| Output type | IGBT inverter cells multilevel PWM | [Us] rated supply voltage | 2.4 kV +/- 10 % |
| Supply frequency | 50 Hz +/- 5 % | Phase | 3 phase |
| Output voltage | <= power supply voltage | Permissible temporary current boost | 1.2 x In 60 s normal duty)<br />1.5 x In 3 s normal duty)<br />1.5 x In 60 s heavy duty)<br />1.8 x In 3 s heavy duty) |
| Speed drive output frequency | 0.1…120 Hz | Frequency resolution | 0.01 Hz |
| Product destination | Synchronous motors<br />Asynchronous motors<br />Permanent magnet motors | Asynchronous motor control profile | Closed loop vector control<br />U/F vector control<br />Energy saving control<br />Vector control with slip compensation in open loop |
| Synchronous motor control profile | Permanent magnet control in open loop<br />Permanent magnet control in close loop<br />Line start permanent magnet motor | Apparent power | 650 kVA |
| Maximum THDI | <3 % IEEE 519-1992 | Power factor | 96 |
| Motor power kW | 410.0 kW heavy duty<br />520.0 kW normal duty | Maximum Horse Power Rating | 549.0 hp heavy duty<br />697.0 hp normal duty |
| Continuous output current | 120.0 A heavy duty<br />150.0 A normal duty | Maximum transient current | 180.0 A 3 s heavy duty)<br />180.0 A 3 s normal duty) |
| Line current | 123.0 A heavy duty<br />180.0 A normal duty | Energy efficiency ratio | 0.985 inverter<br />0.965 total drive including transformer |
| Cable entry | Bottom | Noise level | 90.3 dB |
| EMC filter | Integrated IEC 61800-3 category C3 control<br />Integrated IEC 61800-3 category C4 Power | Display type | 10 inch LCD touch screen multi-language |
| Protection type | Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overvoltages on the DC bus drive<br />Thermal overload for transformer drive<br />Cabinet overheating drive<br />Overcurrent drive<br />Overload drive<br />Short-circuit protection drive<br />IGBT for each cell drive<br />Thermal protection motor<br />Motor phase break motor<br />Motor earth fault motor<br />Break on the control circuit drive<br />Fan monitoring drive | Option card | Slot A communication module Profibus DP V1<br />Slot A communication module PROFINET<br />Slot A communication module DeviceNet<br />Slot A communication module CANopen daisy chain RJ45<br />Slot A communication module CANopen SUB-D 9<br />Slot A communication module CANopen screw terminals<br />Slot A communication module EtherCAT<br />Slot B 5/12 V digital encoder interface module<br />Slot B analog encoder interface module<br />Slot B resolver encoder interface module<br />Slot B HTL encoder interface module<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module |
| Connector type | 2 RJ45 on the control block)Ethernet IP/Modbus TCP<br />1 RJ45 on the control block)Modbus serial | communication port protocol | Ethernet IP/Modbus TCP |
| Supply | Internal supply for digital inputs and PoE 24 V DC 21…27 V, <200 mA overload and short-circuit protection<br />Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />External supply for digital inputs 24 V DC 19…30 V<br />External supply for control circuit 100...240 V AC 47...63 Hz<br />External supply for control circuit 120...370 V DC +/- 10 % 1 kVA<br />Auxiliary power supply 230 V AC +/- 10 %<br />External supply for cooling fan 400 V AC +/- 10 % | Analogue input type | configurable voltage 0...10 V DC 30 kOhm 12 bits<br /> configurable current 0...20 mA 250 Ohm 12 bits |
| Discrete input number | 10 | Discrete input type | DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm<br />DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V)<br />POEA, POEB PWM output enable, 24 V DC <= 30 V)> 2.2 kOhm |
| Analogue output number | 2 | Analogue output type | Configurable voltage 0...10 V DC 470 Ohm 10 bits<br />Configurable current 0...20 mA 500 Ohm 10 bits |
| Discrete output number | 2 | Discrete output type | Logic output <= 30 V DC 100 mA |
| Relay output number | 3 | Relay output type | Configurable relay logic R1 fault relay NO/NC<br />Configurable relay logic R2 sequence relay NO<br />Configurable relay logic R3 sequence relay NO |
| Isolation | Electrical between power and control | Overvoltage category | II IEC 61800-5-1 motor side<br />III IEC 61800-5-1 line side<br />III IEC 61800-5-1 low voltage connections |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6 | Pollution degree | 2 IEC 61800-5-1 |
| Environmental characteristic | 3K3 IEC 60721-3-3<br />3B1 IEC 60721-3-3<br />3C2 IEC 60721-3-3<br />3S1 IEC 60721-3-3<br />3M1 IEC 60721-3-3 | Relative humidity | 5…95 % without condensation IEC 60068-2-3 |
| Ambient air temperature for operation | 32.0000000000…104.0000000000 °F (0…40 °C)<br />104.0000000000…122.0000000000 °F (40…50 °C) with derating factor<br />-13.0000000000…158.0000000000 °F (-25…70 °C) during transport | Ambient Air Temperature for Storage | 32…122 °F (0…50 °C) |
| Operating altitude | <= 3280.84 ft (1000 m) without derating<br />3280.84...6561.68 ft (1000...2000 m) with derating factor | Standards | IEC 61800-3<br />EN/IEC 61800-4<br />IEC 61800-5-1<br />IEC 60529<br />IEEE 519:1992<br />EN/IEC 60076<br />UL 347A |
| marking | CULus<br />CE<br />UKCA |
Specifications may be subject to change without notice