ATV630D55S6
Product ID:28158
Updated: 2026/4/4

Key Features
- 1Deliver 75 HP motor power for demanding industrial applications. 2、Simplify spare parts logistics with a modular design for dynamic maintenance. 3、Integrate Modbus TCP, Ethernet, and Modbus serial for seamless connectivity. 4、Enhance safety with SIL3 Safe Torque Off (STO) for reliable operation. 5、Monitor energy accurately with less than 5% deviation for efficient operation.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Altivar Process ATV600 | Product or Component Type | Variable speed drive |
| Product Specific Application | Process and utilities | Device short name | ATV630 |
| Variant | Standard version | Product destination | Asynchronous motors<br />Synchronous motors |
| EMC filter | Without EMC filter | IP degree of protection | IP20IEC 61800-5-1<br />IP20IEC 60529 |
| [Us] rated supply voltage | 600 V - 15...10 % | Degree of protection | UL type 1 UL 508C |
| Type of cooling | Forced convection | Supply frequency | 50...60 Hz - 5...5 % |
| Maximum Horse Power Rating | 75 hp 600 V normal duty<br />60 hp 600 V heavy duty | Line current | 70.1 A 600 V normal duty)<br />60.4 A 600 V heavy duty) |
| Prospective line Isc | 70 kA | Apparent power | 72.9 kVA 600 V normal duty)<br />62.8 kVA 600 V heavy duty) |
| Continuous output current | 83 A 2.5 kHz normal duty<br />62 A 2.5 kHz heavy duty | Asynchronous motor control profile | Constant torque standard<br />Variable torque standard<br />Optimized torque mode |
| Synchronous motor control profile | Permanent magnet motor<br />Synchronous reluctance motor | Speed drive output frequency | 0.1…500 Hz |
| Nominal switching frequency | 2.5 kHz | Switching frequency | 1...4.9 kHz adjustable<br />2.5...4.9 kHz with derating factor |
| Safety function | STO (safe torque off) SIL 3 | Discrete input logic | Positive logic (source) DI1...DI8), < 5 V, > 11 V<br />Negative logic (sink) DI1...DI8), > 16 V, < 10 V |
| communication port protocol | Modbus TCP<br />Ethernet<br />Modbus serial | Option card | Slot A communication module, Profibus DP V1<br />Slot A communication module, PROFINET<br />Slot A communication module, DeviceNet<br />Slot A communication module, Modbus TCP/EtherNet/IP<br />Slot A communication module, CANopen daisy chain RJ45<br />Slot A communication module, CANopen SUB-D 9<br />Slot A communication module, CANopen screw terminals<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module<br />Slot A communication module, Ethernet IP/Modbus TCP/MD-Link<br /> communication module, BACnet MS/TP<br /> communication module, Ethernet Powerlink |
| Mounting Mode | Wall mount | Maximum transient current | 91.3 A 60 s normal duty)<br />93 A 60 s heavy duty) |
| Phase | 3 phase | Discrete output number | 0 |
| Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA<br />Relay outputs R1A, R1B, R1C 30 V DC 3000 mA<br />Relay outputs R2A, R2C 250 V AC 5000 mA<br />Relay outputs R2A, R2C 30 V DC 5000 mA<br />Relay outputs R3A, R3C 250 V AC 5000 mA<br />Relay outputs R3A, R3C 30 V DC 5000 mA | Output voltage | <= power supply voltage |
| Permissible temporary current boost | 1.1 x In 60 s normal duty)<br />1.5 x In 60 s heavy duty) | Motor slip compensation | Adjustable<br />Can be suppressed<br />Not available in permanent magnet motor law<br />Automatic whatever the load |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s<br />S, U or customized | Physical interface | Ethernet<br />2-wire RS 485 |
| Braking to standstill | By DC injection | Protection type | Thermal protection motor<br />Safe torque off motor<br />Motor phase break motor<br />Thermal protection drive<br />Safe torque off drive<br />Overheating drive<br />Overcurrent between output phases and earth drive<br />Overload of output voltage drive<br />Short-circuit protection drive<br />Motor phase break drive<br />Overvoltages on the DC bus drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overspeed drive<br />Break on the control circuit drive |
| Transmission Rate | 10, 100 Mbits<br />4800 bps, 9600 bps, 19200 bps, 38.4 Kbps | Frequency resolution | Display unit 0.1 Hz<br />Analog input 0.012/50 Hz |
| Transmission frame | RTU | Electrical connection | Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16<br />Line side screw terminal 35...50 mm² AWG 2...AWG 1<br />Motor screw terminal 35...50 mm² AWG 2...AWG 1 |
| Connector type | RJ45 on the remote graphic terminal)Ethernet/Modbus TCP<br />RJ45 on the remote graphic terminal)Modbus serial | Data format | 8 bits, configurable odd, even or no parity |
| Type of polarization | No impedance | Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
| Number of addresses | 1…247 Modbus serial | Method of access | Slave Modbus TCP |
| Supply | External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection<br />Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection | Local signalling | for local diagnostic 3 LEDs<br /> for embedded communication status 3 LEDs (dual colour)<br /> for communication module status 4 LEDs (dual colour)<br /> for presence of voltage 1 LED (red) |
| Width | 13.03 in (331 mm) | Height | 32.4 in (822 mm) |
| Depth | 11.7 in (297 mm) | Net Weight | 121.3 lb(US) (55 kg) |
| Analogue input number | 3 | Analogue input type | AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits<br />AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits<br />AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits |
| Discrete input number | 8 | Discrete input type | DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V) |
| Input compatibility | DI1...DI6 discrete input level 1 PLC IEC 61131-2<br />DI5, DI6 discrete input level 1 PLC IEC 65A-68<br />STOA, STOB discrete input level 1 PLC IEC 61131-2 | Analogue output number | 2 |
| Analogue output type | Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits<br />Software-configurable current AQ1, AQ2 0...20 mA 10 bits<br />Software-configurable current DQ-, DQ+ 30 V DC<br />Software-configurable current DQ-, DQ+ 100 mA | Sampling duration | 2 ms +/- 0.5 ms DI1...DI4) - discrete input<br />5 ms +/- 1 ms DI5, DI6) - discrete input<br />5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input<br />10 ms +/- 1 ms AO1) - analog output |
| Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input<br />+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output | Linearity error | AI1, AI2, AI3 +/- 0.15 % of maximum value analog input<br />AO1, AO2 +/- 0.2 % analog output |
| Relay output number | 3 | Relay output type | Configurable relay logic R1 fault relay NO/NC 100000 cycles<br />Configurable relay logic R2 sequence relay NO 100000 cycles<br />Configurable relay logic R3 sequence relay NO 100000 cycles |
| Refresh time | Relay output R1, R2, R3)5 ms +/- 0.5 ms) | Minimum switching current | Relay output R1, R2, R3 5 mA 24 V DC |
| Maximum switching current | Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC<br />Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC | Isolation | Between power and control terminals |
| Maximum output frequency | 500 kHz | Maximum Input Current per Phase | 70.1 A |
| Quantity per Set | 1 | enclosure mounting | Wall mounted |
| Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth | Noise level | 56 dB |
| Power dissipation in W | Natural convection 247 W 600 V 2.5 kHz<br />Forced convection 965 W 600 V 2.5 kHz | Volume of cooling air | 107255.8 Gal/hr(US) (406 m3/h) |
| Operating position | Vertical +/- 10 degree | Maximum THDI | <48 % with external line choke IEC 61000-3-12 |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6 | Pollution degree | 2 |
| Vibration resistance | 1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6<br />1 gn 13…200 Hz)IEC 60068-2-6 | Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation IEC 60068-2-3 | Ambient air temperature for operation | 5…122 °F (-15…50 °C) without derating)<br />122…140 °F (50…60 °C) with derating factor) |
| Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Operating altitude | <= 3280.84 ft (1000 m) without derating<br />1000...4800 m with current derating 1 % per 100 m |
| Product Certifications | TÜV<br />UL<br />CSA | marking | CE |
| Standards | UL 508C<br />IEC 61800-3<br />IEC 61800-5-1<br />IEC 61000-3-12<br />IEC 60721-3<br />IEC 61508<br />IEC 13849-1 | Overvoltage category | III |
| Regulation loop | Adjustable PID regulator |
Specifications may be subject to change without notice