ATV650D90N4U
Product ID:28869
Updated: 2026/4/4

Key Features
- 1Deliver 125 hp for demanding industrial applications. 2、Ensure robust performance with IP55 enclosure protection. 3、Achieve precise control and energy savings with variable speed. 4、Monitor operations clearly via an intuitive LED display. 5、Install flexibly with wall-mounting option.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | Altivar Process ATV600 | Product or Component Type | Variable speed drive |
| Product Specific Application | Process and utilities | Device short name | ATV650 |
| Variant | Standard version | Product destination | Asynchronous motors<br />Synchronous motors |
| EMC filter | Integrated 492.1 ft (150 m) IEC 61800-3 category C3 | IP degree of protection | IP55IEC 60529<br />IP55IEC 61800-5-1 |
| [Us] rated supply voltage | 380...480 V - 15...10 % | Degree of protection | UL type 12 UL 508C |
| Type of cooling | Forced convection | Supply frequency | 50...60 Hz - 5...5 % |
| Motor power kW | 75 kW heavy duty)<br />90 kW normal duty) | Maximum Horse Power Rating | 100 hp heavy duty<br />125 hp normal duty |
| Line current | 135.8 A 480 V normal duty)<br />134.3 A 380 V heavy duty)<br />118.1 A 480 V heavy duty)<br />156.2 A 380 V normal duty) | Prospective line Isc | 50 kA |
| Apparent power | 98.2 kVA 480 V heavy duty)<br />112.9 kVA 480 V normal duty) | Continuous output current | 145 A 2.5 kHz heavy duty<br />173 A 2.5 kHz normal duty |
| Asynchronous motor control profile | Variable torque standard<br />Optimized torque mode<br />Variable torque standard | Synchronous motor control profile | Synchronous reluctance motor<br />Permanent magnet motor |
| Speed drive output frequency | 0.1…500 Hz | Nominal switching frequency | 2.5 kHz |
| Switching frequency | 2...8 kHz adjustable<br />2.5...8 kHz with derating factor | Safety function | STO (safe torque off) SIL 3 |
| Discrete input logic | Positive logic (source) DI1...DI8), < 5 V, > 11 V<br />Negative logic (sink) DI1...DI8), > 16 V, < 10 V | communication port protocol | Modbus TCP<br />Ethernet<br />Modbus TCP |
| Option card | Slot A communication module, PROFINET<br />Slot A communication module, DeviceNet<br />Slot A communication module, Modbus TCP/EtherNet/IP<br />Slot A communication module, CANopen daisy chain RJ45<br />Slot A communication module, CANopen SUB-D 9<br />Slot A communication module, CANopen screw terminals<br />Slot A/slot B digital and analog I/O extension module<br />Slot A/slot B output relay extension module<br />Slot A communication module, Ethernet IP/Modbus TCP/MD-Link<br /> communication module, BACnet MS/TP<br /> communication module, Ethernet Powerlink<br />Slot A communication module, Profibus DP V1 | Mounting Mode | Wall mount |
| Maximum transient current | 217.5 A 60 s heavy duty)<br />190.3 A 60 s normal duty) | Phase | 3 phase |
| Discrete output number | 0 | Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA<br />Relay outputs R1A, R1B, R1C 30 V DC 3000 mA<br />Relay outputs R2A, R2C 250 V AC 5000 mA<br />Relay outputs R2A, R2C 30 V DC 5000 mA<br />Relay outputs R3A, R3C 250 V AC 5000 mA<br />Relay outputs R3A, R3C 30 V DC 5000 mA |
| Output voltage | <= power supply voltage | Permissible temporary current boost | 1.5 x In 60 s heavy duty)<br />1.1 x In 60 s normal duty) |
| Motor slip compensation | Can be suppressed<br />Automatic whatever the load<br />Adjustable<br />Adjustable | Acceleration and deceleration ramps | Linear adjustable separately from 0.01...9999 s |
| Physical interface | Ethernet<br />2-wire RS 485 | Braking to standstill | By DC injection |
| Protection type | Safe torque off motor<br />Motor phase break motor<br />Thermal protection drive<br />Safe torque off drive<br />Overheating drive<br />Overcurrent between output phases and earth drive<br />Overload of output voltage drive<br />Short-circuit protection drive<br />Motor phase break drive<br />Overvoltages on the DC bus drive<br />Line supply overvoltage drive<br />Line supply undervoltage drive<br />Line supply phase loss drive<br />Overspeed drive<br />Break on the control circuit drive<br />Thermal protection motor | Transmission Rate | 10, 100 Mbits<br />4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
| Frequency resolution | Analog input 0.012/50 Hz<br />Display unit 0.1 Hz | Transmission frame | RTU |
| Electrical connection | Line side screw terminal 95 mm²<br />Motor screw terminal 120 mm²<br />Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 | Connector type | RJ45 on the remote graphic terminal)Modbus serial<br />RJ45 on the remote graphic terminal)Ethernet/Modbus TCP |
| Data format | 8 bits, configurable odd, even or no parity | Type of polarization | No impedance |
| Exchange mode | Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP | Number of addresses | 1…247 Modbus serial |
| Method of access | Slave Modbus TCP | Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection<br />Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection<br />External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection |
| Local signalling | for embedded communication status 3 LEDs (dual colour)<br /> for communication module status 4 LEDs (dual colour)<br /> for presence of voltage 1 LED (red)<br /> for local diagnostic 3 LEDs | Width | 13.6 in (345 mm) |
| Height | 49.2 in (1250 mm) | Depth | 14.8 in (375 mm) |
| Net Weight | 191.8 lb(US) (87 kg) | Analogue input number | 3 |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits<br />AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits<br />AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits | Discrete input number | 8 |
| Discrete input type | DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V) | Input compatibility | DI5, DI6 discrete input level 1 PLC IEC 65A-68<br />STOA, STOB discrete input level 1 PLC IEC 61131-2<br />DI1...DI6 discrete input level 1 PLC IEC 61131-2 |
| Analogue output number | 2 | Analogue output type | Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits<br />Software-configurable current AQ1, AQ2 0...20 mA 10 bits<br />Software-configurable current DQ-, DQ+ 30 V DC<br />Software-configurable current DQ-, DQ+ 100 mA |
| Sampling duration | 5 ms +/- 1 ms DI5, DI6) - discrete input<br />5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input<br />10 ms +/- 1 ms AO1) - analog output<br />2 ms +/- 0.5 ms DI1...DI4) - discrete input | Accuracy | +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output<br />+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input |
| Linearity error | AO1, AO2 +/- 0.2 % analog output<br />AI1, AI2, AI3 +/- 0.15 % of maximum value analog input | Relay output number | 3 |
| Relay output type | Configurable relay logic R2 sequence relay NO 100000 cycles<br />Configurable relay logic R3 sequence relay NO 100000 cycles<br />Configurable relay logic R1 fault relay NO/NC 100000 cycles | Refresh time | Relay output R1, R2, R3)5 ms +/- 0.5 ms) |
| Minimum switching current | Relay output R1, R2, R3 5 mA 24 V DC | Maximum switching current | Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC<br />Relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC<br />Relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC |
| Isolation | Between power and control terminals | Maximum output frequency | 500 kHz |
| Maximum Input Current per Phase | 156.2 A | Quantity per Set | 1 |
| enclosure mounting | Wall mounted | Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
| Noise level | 69.9 dB | Operating position | Vertical +/- 10 degree |
| Maximum THDI | <48 % from 80...100 % of load IEC 61000-3-12 | Electromagnetic compatibility | Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3<br />Electrical fast transient/burst immunity test level 4 IEC 61000-4-4<br />1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5<br />Conducted radio-frequency immunity test level 3 IEC 61000-4-6<br />Electrostatic discharge immunity test level 3 IEC 61000-4-2 |
| Pollution degree | 3 | Vibration resistance | 1 gn 13…200 Hz)IEC 60068-2-6<br />1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6 |
| Shock resistance | 15 gn 11 ms IEC 60068-2-27 | Relative humidity | 5…95 % without condensation IEC 60068-2-3 |
| Ambient air temperature for operation | 104…122 °F (40…50 °C) with derating factor)<br />5…104 °F (-15…40 °C) without derating) | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
| Operating altitude | 1000...4800 m with current derating 1 % per 100 m<br /><= 3280.84 ft (1000 m) without derating | Product Certifications | CSA<br />ATEX zone 2/22<br />ATEX INERIS<br />DNV-GL<br />TÜV<br />UL |
| marking | CE | Standards | IEC 61800-3 environment 1 category C2<br />EN/IEC 61800-3 environment 2 category C3<br />IEC 61800-5-1<br />IEC 61000-3-12<br />IEC 60721-3<br />IEC 61508<br />IEC 13849-1<br />UL 508C |
| Overvoltage category | III | Regulation loop | Adjustable PID regulator |
Specifications may be subject to change without notice