ATV660D45T4

Product ID:28902
Updated: 2026/4/4
schneider ATV660D45T4

Key Features

  • 1Achieve precise high-performance motor control for demanding applications. 2、Utilize forced convection cooling for optimal thermal management. 3、Operate with robust 3-phase power at 460V ±10%. 4、Ensure reliability in temperatures from -10°C to 40°C. 5、Apply this versatile ATV660D45T4 drive across diverse industrial processes.
Product Details
ATV660D45T4
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Altivar 660 Drive System
Product or Component Type
Variable speed drive
Product Specific Application
Process and utilities
Device short name
ATV600
Product destination
Synchronous motors<br />Asynchronous motors
Mounting Mode
Wall-mounted
Function Available
Customised provided equipment<br />Customised option card<br />Customised enclosure colour<br />Customised cable entry
Maximum Horse Power Rating
60 hp
Cable entry
Top<br />Bottom
Colour of enclosure
Light grey RAL 7035)
IP degree of protection
IP23 conforming to UL 508 A<br />IP54
Degree of protection
UL type 1<br />UL type 12<br />UL type 3R
Type of cooling
Forced convection
[Us] rated supply voltage
460 V + 10 % - 15 %
Supply frequency
50/60 Hz +/-5 %
Phase
3 phase
Overvoltage category
III
Asynchronous motor control profile
Constant torque standard<br />Optimized torque mode<br />Variable torque standard
Permissible temporary current boost
1.1 x In 60 s normal duty)<br />1.5 x In 60 s heavy duty)
Nominal switching frequency
2.5 kHz
Switching frequency
0.5...8 kHz adjustable
Motor power kW
45 kW
Maximum THDI
<48 % full load IEEE 519
Energy efficiency ratio
0.95
Pollution degree
2 IEC 60664-1
Vibration resistance
1.5 mm peak to peak 3…13 Hz)IEC 60721-3-3
Relative humidity
95 % without condensation or dripping water IEC 60068-2-78
Ambient air temperature for operation
14…104 °F (-10…40 °C)
Ambient Air Temperature for Storage
-13…149 °F (-25…65 °C)
Operating altitude
3280.84 ft (1000 m) without derating
Standards
UL 508 A

Specifications may be subject to change without notice