ATV660U07U3

Product ID:28988
Updated: 2026/4/4
schneider ATV660U07U3

Key Features

  • 1Deliver 110% nominal torque for 60 seconds in normal duty. 2、Provide 150% torque capability for demanding heavy-duty applications. 3、Ensure operational safety with galvanic isolation and STO features. 4、Achieve precise motor control via prewired remote and potentiometer. 5、Select from power ratings ranging from 1 to 100 horsepower.
Product Details
ATV660U07U3
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Altivar 660 Drive System
Product or Component Type
Variable speed drive
Product Specific Application
Process and utilities
Device short name
ATV600
Product destination
Synchronous motors<br />Asynchronous motors
Mounting Mode
Wall-mounted
Function Available
Customised provided equipment<br />Customised cable entry<br />Customised option card<br />Customised enclosure colour
Maximum Horse Power Rating
1 hp
Cable entry
Top<br />Bottom
Colour of enclosure
Light grey RAL 7035)
IP degree of protection
IP23 conforming to UL 508 A<br />IP54
Degree of protection
UL type 1<br />UL type 12<br />UL type 3R
Type of cooling
Forced convection
[Us] rated supply voltage
230 V + 10 % - 15 %
Supply frequency
50/60 Hz +/-5 %
Phase
3 phase
Overvoltage category
III
Asynchronous motor control profile
Variable torque standard<br />Optimized torque mode<br />Constant torque standard
Permissible temporary current boost
1.1 x In 60 s normal duty)<br />1.5 x In 60 s heavy duty)
Nominal switching frequency
2.5 kHz
Switching frequency
0.5...8 kHz adjustable
Motor power kW
0.75 kW
Maximum THDI
<48 % full load IEEE 519
Energy efficiency ratio
0.95
Pollution degree
2 IEC 60664-1
Vibration resistance
1.5 mm peak to peak 3…13 Hz)IEC 60721-3-3
Relative humidity
95 % without condensation or dripping water IEC 60068-2-78
Ambient air temperature for operation
14…104 °F (-10…40 °C)
Ambient Air Temperature for Storage
-13…149 °F (-25…65 °C)
Operating altitude
3280.84 ft (1000 m) without derating
Standards
UL 508 A

Specifications may be subject to change without notice