BMXAMO0802

Product ID:29542
Updated: 2026/4/3
schneider BMXAMO0802

Key Features

  • 1Deliver high-precision 16-bit analog output for accurate control. 2、Integrate seamlessly with the Modicon X80 platform. 3、Ensure robust performance with EN/IEC/UL 61010-2-201 certification. 4、Achieve fast conversion within 4ms for real-time response. 5、Monitor channel status easily with dedicated diagnostic LEDs.
Product Details
BMXAMO0802
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
Analog output module
Electrical connection
20 ways 1 connector
Isolation between channels
Non isolated
Analogue input resolution
16 bits
Measurement error
<= 0.25 % of full scale 0...60 °C<br />0.1 % of full scale 25 °C
Temperature drift
45 ppm/°C 0...20 mA<br />45 ppm/°C 4...20 mA
Minimum crosstalk attenuation
80 dB
Common mode rejection
80 dB
Isolation voltage
1400 V DC between channels and ground<br />1400 V DC between channels and bus
Detection type
Open circuit 4...20 mA<br />Short circuit 0...20 mA
Load impedance ohmic
<= 350 Ohm 0...20 mA<br /><= 350 Ohm 4...20 mA
Output level
High level
Analogue output number
8
Analogue output type
Current 0...20 mA<br />Current 4...20 mA
Analogue output resolution
16 bits
Supply
Internal power supply via rack
Conversion time
<= 4 ms
Maximum conversion value
0...21 mA 0...20 mA<br />0...21 mA 4...20 mA
Fallback mode
Configurable<br />Predefined
MTBF reliability
1500000 H
Operating altitude
0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor
Status LED
1 LED (Green) RUN<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) ERR<br />1 LED (Red) I/O
Net Weight
0.33 lb(US) (0.15 kg)
Power consumption in W
3.6 W 24 V DC typical<br />3.9 W 24 V DC maximum<br />0.35 W 3.3 V DC typical<br />0.48 W 3.3 V DC maximum
Current consumption
150 mA 3.3 V DC<br />135 mA 24 V DC
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Relative humidity
5…95 % 131 °F (55 °C) without condensation
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility
Product Certifications
CE<br />RCM<br />CSA<br />EAC<br />Merchant Navy<br />UL
Standards
EN/IEC 61010-2-201<br />EN/IEC 61131-2<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201

Specifications may be subject to change without notice