BMXDAI1602

Product ID:29609
Updated: 2026/4/3
schneider BMXDAI1602

Key Features

  • 1Connect 16 discrete inputs with 2-wire or 3-wire proximity sensors. 2、Utilize a 20-way electrical connection for simple integration. 3、Monitor status via LEDs for I/O, error, and operation. 4、Choose isolated or resistive inputs for versatile application needs. 5、Rely on 1500VAC dielectric strength and IP20 protection for durability.
Product Details
BMXDAI1602
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
Discrete input module
Discrete input number
16
Discrete input type
Isolated
input type
Resistive
Discrete input voltage
24 V DC positive or negative<br />24 V AC
Discrete input current
3 mA 24 V AC<br />3.9 mA 24 V DC
Input compatibility
With 2-wire/3-wire proximity sensors IEC 60947-5-2<br />With 2-wire/3-wire proximity sensors AC IEC 61131-2 Type 1
Network Frequency
50/60 Hz
Network frequency limits
47…63 Hz
Sensor power supply
20...26 V AC<br />19...30 V DC
Current state 1 guaranteed
>= 2 mA AC<br />>= 2 mA DC
Current state 0 guaranteed
<= 1 mA AC<br /><= 0.5 mA DC
input impedance
6 kOhm
Insulation resistance
> 10 MOhm 500 V DC
Power dissipation in W
3 W
AC activation response time
15 ms
AC deactivation response time
20 ms
Paralleling of inputs
No
Typical current consumption
76 mA 3.3 V DC
MTBF reliability
1125000 H
Protection type
1 external fuse per group of channel 0.5 A fast blow
Voltage detection threshold
< 14 V AC/DC sensor fault<br />> 18 V AC/DC sensor OK
Status LED
1 LED (Green) module operating (RUN)<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) module error (ERR)<br />1 LED (Red) module I/O
Net Weight
0.254 lb(US) (0.115 kg)
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility
Dielectric strength
1500 V AC 50/60 Hz 1 minute, primary/secondary
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Relative humidity
5…95 % 131 °F (55 °C) without condensation
Operating altitude
0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor

Specifications may be subject to change without notice