BMXDDI1602

Product ID:29544
Updated: 2026/4/3
schneider BMXDDI1602

Key Features

  • 1Process 16 discrete input signals from sensors and devices. 2、Achieve energy efficiency compliant with CSA, IEC, UL, NF standards. 3、Protect against faults with reverse polarity and per-group fusing. 4、Install easily with a compact 0.115 kg design and 20-way connector. 5、Ensure 798,237 hours MTBF for long-term performance in demanding environments.
Product Details
BMXDDI1602
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
Discrete input module
Discrete input number
16
Discrete input type
Isolated
input type
Current sink (logic positive)
Discrete input voltage
24 V DC positive
Discrete input current
3.5 mA
Input compatibility
With 2-wire/3-wire proximity sensors IEC 60947-5-2<br />With 2-wire/3-wire proximity sensors IEC 61131-2 type 3
Sensor power supply
19...30 V
Current state 1 guaranteed
>= 2 mA
Current state 0 guaranteed
<= 1.5 mA
input impedance
6800 Ohm
Insulation resistance
> 10 MOhm 500 V DC
Power dissipation in W
2.5 W
DC typical response time
4 ms
DC maximum response time
7 ms
Paralleling of inputs
Yes
Typical current consumption
76 mA 3.3 V DC
MTBF reliability
775000 H
Protection type
1 external fuse per group of channel 0.5 A fast blow<br /> reverse polarity protection
Voltage detection threshold
< 14 V DC sensor fault<br />> 18 V DC sensor OK
Status LED
1 LED (Green) module operating (RUN)<br />1 LED per channel (Green) channel diagnostic<br />1 LED (Red) module error (ERR)<br />1 LED (Red) module I/O
Net Weight
0.254 lb(US) (0.115 kg)
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility
Environmental characteristic
Fungal spore resistant class 3B2
Dielectric strength
1500 V AC 50/60 Hz 1 minute, primary/secondary
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Relative humidity
5…95 % 131 °F (55 °C) without condensation
Operating altitude
0...6561.68 ft (0...2000 m)<br />2000...5000 m with derating factor

Specifications may be subject to change without notice