  • 1Deliver robust performance in demanding PLC applications. 2、Configure for various input types including proximity sensors. 3、Integrate seamlessly with standard 24 V DC power systems. 4、Reduce energy costs with only 4.3 mA consumption per input. 5、Ensure reliable connectivity with two 28-pin connectors.
Product Details
BMXMSP0200
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
Modicon X80
Product or Component Type
PTO module
Number of Channels
2
Number of inputs
4
Discrete input type
Current sink yes origin input IEC 61131-2 type 3<br />Current sink yes proximity input and limit switch input IEC 61131-2 type 3<br />Current sink or source counter in position input IEC 61131-2 type 3<br />Current sink or source drive ready, emergency input IEC 61131-2 type 3
Input compatibility
2-wire/3-wire proximity sensor 19.2…30 V IEC 947-5-2
Output compatibility
Signal converter (USIC)<br />RS422, 7 mA input<br />Source input, 5 V to 24 V
Output frequency
200 kHz <1.6 ft (0.5 m) with USIC and VW3M8210R05<br />100 kHz <16.4 ft (5 m) with the normal source input circuit<br />200 kHz <32.8 ft (10 m) with the RS422 compatible circuits
Operating threshold
> 12 V no error supply voltage<br />> 8 V error supply voltage
Input voltage
24 V DC
Input current
4.3 mA
Voltage state 1 guaranteed
>= 11 V
Current consumption
35 mA 24 V DC preactuator<br />150 mA 3.3 V DC typical<br />200 mA 3.3 V DC maximum
Current state 1 guaranteed
>= 2 mA
Voltage state 0 guaranteed
5 V
Current state 0 guaranteed
<= 1.5 mA
Response time
< 200 µs for position completed input and drive ready input<br />< 60 µs for origin input and proximity input
Number of outputs
1 pulse output<br />2 auxiliary output
Preactuator voltage detection threshold
< 8 V error preactuator voltage auxiliary output<br />< 8 V no error preactuator voltage auxiliary output<br />> 14 V error preactuator voltage pulse output<br />> 14 V no error preactuator voltage pulse output
Output voltage
24 V DC
Output voltage limits
19...30 V
Discrete output current
50 mA
Current per channel
0.4 A
Maximum leakage current
0.05 mA at state 0
[Ures] residual voltage
0.15 V at state 1
Response time on output
1.2...1.5 ms on appearance<br />1.2...1.5 ms on disappearance
Load impedance ohmic
15000 Ohm
Output overload protection
By current limiter and electronic circuit breaker
Output short-circuit protection
By current limiter and electronic circuit breaker
Reverse polarity protection
By reverse mounting diode on output<br />Integrated on input
Insulation between channels
No insulated
Insul btwn prim and second
1500 Vrms
Insulation resistance
> 10 MOhm
Local signalling
for module operating (RUN) 1 LED (green)<br /> for external fault (I/O) 1 LED (red)<br /> for internal fault, module failure (ERR) 1 LED (red)<br /> for download (DL) 1 LED (green)<br /> for channel status (CH00) 8 LEDs (green)<br /> for channel status (CH01) 8 LEDs (green)
Electrical connection
2 connectors 28 pins
Module format
Standard
Product certifications
CE<br />UL<br />CSA<br />RCM<br />EAC<br />Merchant Navy<br />ATEX zone 2/22<br />IECEx zone 2/22
Ambient Air Temperature for Operation
-13…158 °F (-25…70 °C)
Derating factor
Without
Directives
2014/35/EU - low voltage directive<br />2014/30/EU - electromagnetic compatibility<br />2014/34/EU - ATEX directive
Standards
EN/IEC 61131-2<br />EN/IEC 61010-2-201<br />UL 61010-2-201<br />CSA C22.2 No 61010-2-201<br />IACS E10<br />EN/IEC 61000-6-5, interface type 1 and type 2<br />EN/IEC 61850-3, location G<br />EN/IEC 60079-0
Environmental characteristic
Hazardous location class I division 2