LC1D40004P7
Product ID:31659
Updated: 2026/4/5

Key Features
- 1Achieve high 18.5 kW switching capacity for efficient power control. 2、Mount conveniently on standard DIN rails for quick installation. 3、Utilize four normally open power contacts for versatile circuit design. 4、Operate with standard 230V AC control voltage for easy integration. 5、Handle robust loads with a maximum 40A operating current.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | TeSys Deca | Product or Component Type | Contactor |
| Device short name | LC1D | Contactor application | Resistive load |
| Utilisation category | AC-1<br />AC-3<br />AC-3e<br />AC-4 | Poles description | 4P |
| [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz | [Ie] rated operational current | 60 A (at <140 °F (60 °C)) AC AC-1 for power circuit |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz | compatibility code | LC1D |
| Pole contact composition | 4 NO | Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for control circuit<br />60 A (at 140 °F (60 °C)) for power circuit | Irms rated making capacity | 140 A AC for control circuit conforming to IEC 60947-5-1<br />800 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 800 A at 440 V for power circuit conforming to IEC 60947 | Associated fuse rating | 10 A gG for control circuit conforming to IEC 60947-5-1<br />80 A gG at <= 690 V coordination type 1 for power circuit<br />80 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 1.5 mOhm - Ith 60 A 50 Hz for power circuit | Power dissipation per pole | 5.4 W AC-1 |
| [Ui] rated insulation voltage | Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1 | Overvoltage category | III |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947 | Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 6000000 cycles | Control circuit type | AC 50/60 Hz standard |
| Coil technology | Without built-in bidirectional peak limiting diode suppressor | Control circuit voltage limits | 0.3...0.6 Uc 140 °F (60 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc 140 °F (60 °C) operational AC 50 Hz<br />0.85...1.1 Uc 140 °F (60 °C) operational AC 60 Hz |
| Inrush power in VA | 140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C)) | Hold-in power consumption in VA | 13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Heat dissipation | 4…5 W at 50/60 Hz for control circuit | Operating time | 12...26 ms closing<br />4...19 ms opening |
| Maximum operating rate | 3600 cyc/h 140 °F (60 °C) | Connections - terminals | Control circuit: screw clamp terminal 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminal 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end<br />Power circuit: screw clamp terminal 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end<br />Power circuit: screw clamp terminal 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: solid without cable end<br />Power circuit: screw clamp terminal 2 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end |
| Tightening torque | Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 6 mm<br />Power circuit 44.3 lbf.in (5 N.m) screw clamp terminal flat Ø 8 mm | Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1 |
| Minimum switching voltage | 17 V for control circuit | Minimum switching current | 5 mA for control circuit |
| Insulation resistance | > 10 MOhm for control circuit | Non-overlap time | 1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts |
| Mounting Support | Rail<br />Plate | Standards | CSA C22.2 No 14<br />EN 60947-5-1<br />UL 508<br />IEC 60947-4-1<br />EN 60947-4-1<br />IEC 60947-5-1 |
| Product Certifications | LROS (Lloyds register of shipping)<br />GL<br />DNV<br />UL<br />CSA<br />RINA<br />BV<br />CCC<br />GOST<br />UKCA | IP degree of protection | IP2X IEC 60529<br />IP2X VDE 0106 |
| Protective treatment | TH 3)IEC 60068 | Permissible ambient air temperature around the device | 23…140 °F (-5…60 °C)<br />-40…158 °F (-40…70 °C) at Uc |
| Operating altitude | 9842.52 ft (3000 m) without derating | Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 | Mechanical robustness | Shocks contactor open 8 Gn for 11 ms) <br />Shocks contactor closed 10 Gn for 11 ms) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) |
| Height | 5.0000000000 in (127 mm) | Width | 3.3 in (85 mm) |
| Depth | 4.9 in (125 mm) | Net Weight | 3.17 lb(US) (1.44 kg) |
Specifications may be subject to change without notice