LC1D40U7
Product ID:31746
Updated: 2026/4/5

Key Features
- 1Meet IEC standards for reliable and durable performance. 2、Handle 40A load and 160A switching current efficiently. 3、Mount on DIN rails for quick and secure installation. 4、Ensure compliance with US EAR99 and EU standards. 5、Suit various industrial 3-phase motor applications.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Range of Product | TeSys Deca |
| Product or Component Type | Contactor | Device short name | LC1D |
| Contactor application | Motor control<br />Resistive load | Utilisation category | AC-4<br />AC-1<br />AC-2<br />AC-3<br />AC-3e |
| Poles description | 3P | [Ue] rated operational voltage | Power circuit <= 690 V AC 25...400 Hz |
| [Ie] rated operational current | 40 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit<br />40 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit | [Uc] control circuit voltage | 240 V AC 50/60 Hz |
| Motor power kW | 18.5 kW at 380...400 V AC 50 Hz (AC-3)<br />22 kW at 500 V AC 50 Hz (AC-3)<br />30 kW at 660...690 V AC 50 Hz (AC-3)<br />22 kW at 1000 V AC 50 Hz (AC-3)<br />22 kW at 415 V AC 50 Hz (AC-3)<br />22 kW at 440 V AC 50 Hz (AC-3)<br />11 kW at 220...230 V AC 50 Hz (AC-3)<br />9 kW at 400 V AC 50 Hz (AC-4)<br />18.5 kW at 380...400 V AC 50 Hz (AC-3e)<br />22 kW at 500 V AC 50 Hz (AC-3e)<br />30 kW at 660...690 V AC 50 Hz (AC-3e)<br />22 kW at 1000 V AC 50 Hz (AC-3e)<br />22 kW at 415 V AC 50 Hz (AC-3e)<br />22 kW at 440 V AC 50 Hz (AC-3e)<br />11 kW at 220...230 V AC 50 Hz (AC-3e) | Maximum Horse Power Rating | 3 hp at 115 V AC 60 Hz for 1 phase motors<br />5 hp at 230/240 V AC 60 Hz for 1 phase motors<br />10 hp at 200/208 V AC 60 Hz for 3 phase motors<br />10 hp at 230/240 V AC 60 Hz for 3 phase motors<br />30 hp at 460/480 V AC 60 Hz for 3 phase motors<br />30 hp at 575/600 V AC 60 Hz for 3 phase motors |
| compatibility code | LC1D | Pole contact composition | 3 NO |
| Protective cover | With | [Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) for control circuit<br />60 A (at 140 °F (60 °C)) for power circuit |
| Irms rated making capacity | 800 A at 440 V for power circuit conforming to IEC 60947<br />140 A AC for control circuit conforming to IEC 60947-5-1 | Rated breaking capacity | 800 A at 440 V for power circuit conforming to IEC 60947 |
| Associated fuse rating | 10 A gG for control circuit conforming to IEC 60947-5-1<br />80 A gG at <= 690 V coordination type 1 for power circuit<br />80 A gG at <= 690 V coordination type 2 for power circuit | Power dissipation per pole | 5.4 W AC-1<br />2.4 W AC-3<br />2.4 W AC-3e |
| [Ui] rated insulation voltage | Control circuit 600 V CSA<br />Control circuit 600 V UL<br />Power circuit 600 V CSA<br />Power circuit 600 V UL<br />Control circuit 690 V IEC 60947-1<br />Power circuit 690 V IEC 60947-1 | Overvoltage category | III |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947 | Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Mechanical durability | 6000000 cycles | Control circuit type | AC 50/60 Hz |
| Coil technology | Without built-in bidirectional peak limiting diode suppressor | Control circuit voltage limits | 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz<br />0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz<br />0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz<br />1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz |
| Inrush power in VA | 140 VA cos phi 0.75 (at 68 °F (20 °C))<br />160 VA cos phi 0.75 (at 68 °F (20 °C)) | Hold-in power consumption in VA | 13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))<br />15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Heat dissipation | 4…5 W at 50/60 Hz for control circuit | Operating time | 4...19 ms opening<br />12...26 ms closing |
| Maximum operating rate | 3600 cyc/h 140 °F (60 °C) | Connections - terminals | Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: rigid<br />Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end<br />Control circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: rigid<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: rigid<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…16 mm²) - cable stiffness: flexible without cable end<br />Power circuit: screw terminals 1 0.004…0.04 in² (2.5…25 mm²) - cable stiffness: flexible with cable end<br />Power circuit: screw terminals 2 0.004…0.02 in² (2.5…10 mm²) - cable stiffness: flexible with cable end |
| Tightening torque | Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal flat Ø 6 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal Philips No 2<br />Power circuit 44.3 lbf.in (5 N.m) screw terminal flat Ø 6 to Ø 8 mm<br />Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminal pozidriv No 2 | Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1<br />Mirror contact 1 NC IEC 60947-4-1 | Minimum switching voltage | 17 V for control circuit |
| Minimum switching current | 5 mA for control circuit | Insulation resistance | > 10 MOhm for control circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contacts<br />1.5 ms on energisation between NC and NO contacts | Mounting Support | Rail<br />Plate |
| Standards | IEC 60947-5-1<br />IEC 60947-4-1<br />UL 508<br />EN 60947-4-1<br />EN 60947-5-1<br />CSA C22.2 No 14 | Product Certifications | GL<br />BV<br />DNV<br />LROS (Lloyds register of shipping)<br />RINA<br />UL<br />CCC<br />CSA<br />GOST<br />UKCA<br />CB |
| IP degree of protection | IP2X IEC 60529<br />IP2X VDE 0106 | Climatic withstand | IACS E10 exposure to damp heat |
| Operating altitude | 0...9842.52 ft (0...3000 m) | Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 | Mechanical robustness | Shocks contactor opened 10 Gn for 11 ms) <br />Shocks contactor closed 15 Gn for 11 ms) <br />Vibrations contactor opened 2 Gn, 5...300 Hz) <br />Vibrations contactor closed 4 Gn, 5...300 Hz) |
| Height | 5.0000000000 in (127 mm) | Width | 3.0 in (75 mm) |
| Depth | 4.7 in (119 mm) | Net Weight | 3.09 lb(US) (1.4 kg) |
Specifications may be subject to change without notice