LC1F115B6
Product ID:32685
Updated: 2026/4/5

Key Features
- 1Ensure high reliability with extended mechanical and electrical life. 2、Handle resistive loads up to 1000 Amps and inductive loads up to 800 Amps. 3、Control motors rated up to 800 HP at 480 Vac or 900 HP at 600 Vac. 4、Simplify control with a 24V AC 60Hz rated coil. 5、Secure connections using the 3 pole design with screw terminals.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Range of Product | TeSys F |
| Product or Component Type | Contactor | Device short name | LC1F |
| Contactor application | Resistive load<br />Motor control | Utilisation category | AC-3<br />AC-1 |
| Poles description | 3P | [Ue] rated operational voltage | <= 690 V AC 50/60 Hz<br /><= 460 V DC |
| [Uc] control circuit voltage | 24 V AC 60 Hz | [Ie] rated operational current | 200 A (at <104 °F (40 °C)) at <= 440 V AC-1<br />115 A (at <131 °F (55 °C)) at <= 440 V AC-3 |
| [Uimp] rated impulse withstand voltage | 8 kV | [Ith] conventional free air thermal current | 200 A (at 104 °F (40 °C)) |
| Rated breaking capacity | 920 A conforming to IEC 60947-4-1 | [Icw] rated short-time withstand current | 1100 A 104 °F (40 °C) - 10 s<br />640 A 104 °F (40 °C) - 30 s<br />520 A 104 °F (40 °C) - 1 min<br />400 A 104 °F (40 °C) - 3 min<br />320 A 104 °F (40 °C) - 10 min |
| Associated fuse rating | 125 A aM at <= 440 V<br />200 A gG at <= 440 V | Average impedance | 0.37 mOhm - Ith 200 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C | Power dissipation per pole | 15 W AC-1<br />5 W AC-3 |
| Overvoltage category | III | power pole contact composition | 3 NO |
| Motor power kW | 55 kW at 380...400 V AC 50/60 Hz (AC-3)<br />59 kW at 415 V AC 50/60 Hz (AC-3)<br />59 kW at 440 V AC 50/60 Hz (AC-3)<br />75 kW at 500 V AC 50/60 Hz (AC-3)<br />80 kW at 660...690 V AC 50/60 Hz (AC-3)<br />30 kW at 220...230 V AC 50/60 Hz (AC-3)<br />18.5 kW at 400 V AC 50/60 Hz (AC-4) | Control circuit voltage limits | Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) |
| Mechanical durability | 10 Mcycles | Inrush power in VA | 660 VA, 60 Hz 0.3 68 °F (20 °C)) |
| Hold-in power consumption in VA | 55 VA, 60 Hz 0.3 68 °F (20 °C)) | Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| Operating time | 23...35 ms closing<br />5...15 ms opening | Connections - terminals | Power circuit bar 2 20 x 3 mm<br />Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)<br />Power circuit connector 1 0.1 in² (95 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end |
| Tightening torque | Power circuit 88.5 lbf.in (10 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m) | Mounting Support | Plate |
| Heat dissipation | 12…16 W | Standards | IEC 60947-4-1<br />IEC 60947-1<br />EN 60947-4-1<br />EN 60947-1<br />JIS C8201-4-1 |
| Product Certifications | DNV<br />CCC<br />ABS<br />LROS (Lloyds register of shipping)<br />UL<br />RMRoS<br />CB<br />BV<br />RINA<br />UKCA | compatibility code | LC1F |
| Control circuit type | AC 60 Hz | IP degree of protection | IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106 |
| Protective treatment | TH | Ambient Air Temperature for Operation | -40…140 °F (-40…60 °C) |
| Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) | Permissible ambient air temperature around the device | 140…158 °F (60…70 °C) at Uc |
| Height | 6.4 in (162 mm) | Width | 6.4 in (163.3 mm) |
| Depth | 6.7 in (171 mm) | Operating altitude | 9842.52 ft (3000 m) without derating |
| Net Weight | 7.56 lb(US) (3.43 kg) |
Specifications may be subject to change without notice