LC1F115N522L
Product ID:32551
Updated: 2026/4/5

Key Features
- 1Handle high currents up to 115A reliably. 2、Ensure compatibility with 24 to 575V AC systems. 3、Configure with 1NO contact and no coil for reversing. 4、Mount easily on DIN rails for quick installation. 5、Select the reliable TeSys F Series for efficiency.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range of Product | TeSys F | Product or Component Type | Contactor |
| Device short name | LC1F | Contactor application | Motor control<br />Resistive load |
| Utilisation category | AC-4<br />AC-1<br />AC-3 | Poles description | 3P |
| [Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<br /> <= 460 V DC | [Uc] control circuit voltage | 415 V AC 50 Hz |
| [Ie] rated operational current | 200 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />115 A (at <131 °F (55 °C)) at <= 440 V AC AC-3 | [Uimp] rated impulse withstand voltage | 8 kV |
| [Ith] conventional free air thermal current | 200 A (at 104 °F (40 °C)) | Rated breaking capacity | 920 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 1100 A 104 °F (40 °C) - 10 s<br />640 A 104 °F (40 °C) - 30 s<br />520 A 104 °F (40 °C) - 1 min<br />400 A 104 °F (40 °C) - 3 min<br />320 A 104 °F (40 °C) - 10 min | Associated fuse rating | 125 A aM at <= 440 V<br />200 A gG at <= 440 V |
| Average impedance | 0.37 mOhm - Ith 200 A 50 Hz | [Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C |
| Power dissipation per pole | 15 W AC-1<br />5 W AC-3 | Overvoltage category | III |
| power pole contact composition | 3 NO | Auxiliary contact composition | 2 NO + 2 NC |
| Motor power kW | 55 kW at 380...400 V AC 50/60 Hz (AC-3)<br />59 kW at 415 V AC 50/60 Hz (AC-3)<br />59 kW at 440 V AC 50/60 Hz (AC-3)<br />75 kW at 500 V AC 50/60 Hz (AC-3)<br />80 kW at 660...690 V AC 50/60 Hz (AC-3)<br />65 kW at 1000 V AC 50/60 Hz (AC-3)<br />30 kW at 220...230 V AC 50/60 Hz (AC-3)<br />18.5 kW at 400 V AC 50/60 Hz (AC-4) | motor power HP (UL / CSA) | 30 hp at 200 V AC<br />40 hp at 230 V AC<br />75 hp at 460 V AC<br />100 hp at 575 V AC |
| Control circuit voltage limits | Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C)) | Mechanical durability | 10 Mcycles |
| Inrush power in VA | 550 VA, 50 Hz 0.3 68 °F (20 °C)) | Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| Operating time | 23...35 ms closing<br />5...15 ms opening | Connections - terminals | Power circuit 2 bars 20 x 3 mm<br />Power circuit lugs-ring terminals 1 0.1 in² (95 mm²)<br />Power circuit connector 1 0.1 in² (95 mm²)<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection |
| Tightening torque | Power circuit 88.5 lbf.in (10 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m) | Mounting Support | Plate |
| Heat dissipation | 12…16 W | Standards | EN 60947-1<br />JIS C8201-4-1<br />IEC 60947-1<br />EN 60947-4-1<br />IEC 60947-4-1 |
| Product Certifications | UL<br />RMRoS<br />RINA<br />BV<br />LROS (Lloyds register of shipping)<br />ABS<br />CB<br />CCC<br />DNV | Hold-in power consumption in VA | 45 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| IP degree of protection | IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106 | Protective treatment | TH |
| Ambient Air Temperature for Operation | -40…140 °F (-40…60 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
| Permissible ambient air temperature around the device | 140…158 °F (60…70 °C) at Uc | Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed6 Gn, 5...300 Hz<br />Shocks contactor open9 Gn for 11 ms<br />Shocks contactor closed15 Gn for 11 ms |
| Height | 10.4 in (265 mm) | Width | 6.4 in (163.3 mm) |
| Depth | 6.7 in (171 mm) | Operating altitude | 9842.52 ft (3000 m) without derating |
Specifications may be subject to change without notice