LC1F1504G6

Product ID:32582
Updated: 2026/4/5
schneider LC1F1504G6

Key Features

  • 1Handle up to 150A at 600V AC for demanding applications. 2、Control motors up to 75kW @400V with reliable performance. 3、Ensure safety and compliance with IEC 60947-4-1 standards. 4、Maximize uptime with a durable 2400 cycles/hour rating. 5、Simplify procurement with available stock and fast shipping.
Product Details
LC1F1504G6
schneider

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Uc] control circuit voltage
120 V AC 60 Hz
[Ie] rated operational current
250 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
250 A (at 104 °F (40 °C))
Rated breaking capacity
1200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1200 A 104 °F (40 °C) - 10 s<br />700 A 104 °F (40 °C) - 30 s<br />600 A 104 °F (40 °C) - 1 min<br />450 A 104 °F (40 °C) - 3 min<br />350 A 104 °F (40 °C) - 10 min
Associated fuse rating
160 A aM at <= 440 V<br />250 A gG at <= 440 V
Average impedance
0.35 mOhm - Ith 250 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
22 W AC-1
Overvoltage category
III
power pole contact composition
4 NO
motor power HP (UL / CSA)
40 hp at 200 V AC<br />50 hp at 230 V AC<br />100 hp at 460 V AC<br />125 hp at 575 V AC
Control circuit voltage limits
Operational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C))<br />Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in VA
660 VA, 60 Hz 0.3 68 °F (20 °C))
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
23...35 ms closing<br />5...15 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bolted connection<br />Power circuit 2 bars 25 x 3 mm<br />Power circuit lugs-ring terminals 1 0.2 in² (120 mm²)<br />Power circuit connector 1 0.2 in² (120 mm²)
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 159.3 lbf.in (18 N.m)
Mounting Support
Plate
Heat dissipation
12…16 W
Standards
EN 60947-4-1<br />IEC 60947-1<br />EN 60947-1<br />IEC 60947-4-1<br />JIS C8201-4-1
Product Certifications
DNV<br />CB<br />LROS (Lloyds register of shipping)<br />RMRoS<br />ABS<br />UL<br />RINA<br />CCC<br />BV
Hold-in power consumption in VA
55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
-40…140 °F (-40…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
140…158 °F (60…70 °C)
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed6 Gn, 5...300 Hz<br />Shocks contactor open9 Gn for 11 ms<br />Shocks contactor closed15 Gn for 11 ms
Height
6.7 in (170 mm)
Width
7.9 in (200.5 mm)
Depth
6.7 in (171 mm)
Operating altitude
9842.52 ft (3000 m) without derating

Specifications may be subject to change without notice