LC1F225
Product ID:32609
Updated: 2026/4/5

Key Features
- 1Handle up to 225A for robust motor control. 2、Install easily with a compact 45mm width design. 3、Comply with IEC, UL, CSA, CCC, EAC, Marine standards. 4、Ensure high reliability in demanding environments. 5、Suit various applications like pumps, fans, and conveyors.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Product name | TeSys F |
| Product or Component Type | Contactor | Device short name | LC1F |
| Contactor application | Motor control<br />Resistive load | Utilisation category | AC-4<br />AC-1<br />AC-3 |
| Poles description | 3P | power pole contact composition | 3 NO |
| [Ue] rated operational voltage | <= 690 V AC 50/60 Hz<br /> <= 460 V DC | [Ie] rated operational current | 315 A 104 °F (40 °C)) <= 440 V AC-1<br />225 A 131 °F (55 °C)) <= 440 V AC-3 |
| Motor power kW | 110 kW at 380...400 V AC 50/60 Hz (AC-3)<br />110 kW at 415 V AC 50/60 Hz (AC-3)<br />110 kW at 440 V AC 50/60 Hz (AC-3)<br />129 kW at 500 V AC 50/60 Hz (AC-3)<br />63 kW at 220...240 V AC 50/60 Hz (AC-3)<br />129 kW at 660...690 V AC 50/60 Hz (AC-3)<br />40 kW at 400 V AC 50/60 Hz (AC-4) | [Uc] control circuit voltage | 24...575 V AC 40...400 Hz with LX9 coil<br />24...460 V DC with LX4 coil<br />100...250 V AC 50/60 Hz with LXE coil<br />100...380 V DC with LXE coil |
| [Uimp] rated impulse withstand voltage | 8 kV | Overvoltage category | III |
| [Ith] conventional free air thermal current | 315 A (at 104 °F (40 °C)) | Irms rated making capacity | 2250 A conforming to IEC 60947-4-1 |
| Rated breaking capacity | 1800 A conforming to IEC 60947-4-1 | [Icw] rated short-time withstand current | 1800 A 104 °F (40 °C) - 10 s<br />1000 A 104 °F (40 °C) - 30 s<br />850 A 104 °F (40 °C) - 1 min<br />560 A 104 °F (40 °C) - 3 min<br />440 A 104 °F (40 °C) - 10 min |
| Associated fuse rating | 315 A gG at <= 440 V<br />250 A aM at <= 440 V | Average impedance | 0.32 mOhm - Ith 315 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C | Power dissipation per pole | 32 W AC-1<br />16 W AC-3 |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil<br />Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.15...0.2 Uc DC with LX4 coil<br />Operational: 85...275 V AC 50/60 Hz with LXE coil<br />Drop-out: 0...60 V AC 50/60 Hz with LXE coil<br />Operational: 85...418 V DC with LXE coil<br />Drop-out: 0...45 V DC with LXE coil | Heat dissipation | 8…9.8 W<br />2.2…2.5 W |
| Operating time | 35 ms closing with LX9 coil<br />130 ms opening with LX9 coil<br />30...40 ms closing with LX4 coil<br />30...50 ms opening with LX4 coil<br />40...80 ms closing with LXE coil<br />6...54 ms opening with LXE coil | Mounting Support | Plate |
| Standards | JIS C8201-4-1<br />IEC 60947-4-1<br />IEC 60947-1<br />EN 60947-4-1<br />EN 60947-1 | Product Certifications | UL<br />LROS (Lloyds register of shipping)<br />BV<br />CB<br />ABS<br />DNV<br />CSA<br />RMRoS<br />RINA<br />UKCA |
| Connections - terminals | Power circuit lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit connector 1 0.3 in² (185 mm²)<br />Power circuit bar 2 32 x 4 mm<br />Power circuit bolted connection<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1.0 0.0004…0.004 in² (0.25…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)solid without cable end | Tightening torque | Power circuit 309.8 lbf.in (35 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)<br />Control circuit 5.3 lbf.in (0.6 N.m) |
| Mechanical durability | 10 Mcycles | Inrush power in VA | 950…1180 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX9 coil<br />737…902 VA (at 68 °F (20 °C))with LX4 coil<br />280…310 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />270…320 VA (at 68 °F (20 °C))with LXE coil |
| Hold-in power consumption in VA | 8.9…10.9 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX9 coil<br />4.13…5.07 VA (at 68 °F (20 °C))with LX4 coil<br />4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />2.5…4.0 VA (at 68 °F (20 °C))with LXE coil | Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| compatibility code | LC1F | IP degree of protection | IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106 |
| Protective treatment | TH | Ambient Air Temperature for Operation | 23…131 °F (-5…55 °C) |
| Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) | Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) |
| Operating altitude | 9842.52 ft (3000 m) without derating | Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open7 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms) |
| Height | 7.8 in (197 mm) | Width | 6.6 in (168.5 mm) |
| Depth | 7.1 in (181 mm) | Net Weight | 12.24 lb(US) (5.55 kg) |
Specifications may be subject to change without notice