Key Features
- 1Achieve high-power control with a 225A rating at 440Vac. 2、Ensure long-term reliability with 10 million mechanical operations. 3、Handle versatile applications for motors and resistive loads. 4、Simplify system integration using flexible auxiliary components. 5、Meet global safety standards including IEC, UL, and CSA.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Range of Product | TeSys F |
| Product or Component Type | Contactor | Device short name | LC1F |
| Contactor application | Motor control<br />Resistive load | Utilisation category | AC-1<br />AC-4<br />AC-3 |
| Poles description | 3P | [Ue] rated operational voltage | <= 460 V DC<br /><= 690 V AC 50/60 Hz |
| [Uc] control circuit voltage | 220 V AC 40...400 Hz | [Ie] rated operational current | 315 A (at <104 °F (40 °C)) at <= 440 V AC-1<br />225 A (at <131 °F (55 °C)) at <= 440 V AC-3 |
| [Uimp] rated impulse withstand voltage | 8 kV | [Ith] conventional free air thermal current | 315 A (at 104 °F (40 °C)) |
| Rated breaking capacity | 1800 A conforming to IEC 60947-4-1 | [Icw] rated short-time withstand current | 1800 A 104 °F (40 °C) - 10 s<br />1000 A 104 °F (40 °C) - 30 s<br />850 A 104 °F (40 °C) - 1 min<br />560 A 104 °F (40 °C) - 3 min<br />440 A 104 °F (40 °C) - 10 min |
| Associated fuse rating | 315 A gG at <= 440 V<br />250 A aM at <= 440 V | Average impedance | 0.32 mOhm - Ith 315 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C | Power dissipation per pole | 32 W AC-1<br />16 W AC-3 |
| Overvoltage category | III | power pole contact composition | 3 NO |
| Motor power kW | 110 kW at 380...400 V AC 50/60 Hz (AC-3)<br />110 kW at 415 V AC 50/60 Hz (AC-3)<br />110 kW at 440 V AC 50/60 Hz (AC-3)<br />129 kW at 500 V AC 50/60 Hz (AC-3)<br />129 kW at 660...690 V AC 50/60 Hz (AC-3)<br />63 kW at 220...230 V AC 50/60 Hz (AC-3)<br />40 kW at 400 V AC 50/60 Hz (AC-4) | Control circuit voltage limits | Operational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C))<br />Drop-out 0.2...0.55 Uc 40...400 Hz 131 °F (55 °C)) |
| Mechanical durability | 10 Mcycles | Inrush power in VA | 1070 VA, 40...400 Hz 0.9 68 °F (20 °C)) |
| Hold-in power consumption in VA | 9.9 VA, 40...400 Hz 0.9 68 °F (20 °C)) | Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| Operating time | 35 ms closing at Uc) <br />130 ms opening at Uc) | Connections - terminals | Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 32 x 4 mm<br />Power circuit lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit connector 1 0.3 in² (185 mm²)<br />Power circuit bolted connection |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m) | Mounting Support | Plate |
| Heat dissipation | 8…9.8 W | motor power range | 55…100 kW 200…240 V 3 phase<br />110…220 kW 480…500 V 3 phase<br />110…220 kW 380…440 V 3 phase |
| Motor starter type | Direct on-line contactor | Contactor coil voltage | 220 V AC standard |
| Standards | IEC 60947-1<br />JIS C8201-4-1<br />EN 60947-1<br />IEC 60947-4-1<br />EN 60947-4-1 | Product Certifications | RINA<br />BV<br />CSA<br />UL<br />LROS (Lloyds register of shipping)<br />DNV<br />RMRoS<br />ABS<br />CB<br />UKCA |
| Compatibility code | LC1F | Control circuit type | AC 40...400 Hz |
| IP degree of protection | IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106 | Protective treatment | TH |
| Ambient Air Temperature for Operation | 23…131 °F (-5…55 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
| Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) | Height | 7.8 in (197 mm) |
| Width | 6.6 in (168.5 mm) | Depth | 7.1 in (181 mm) |
| Operating altitude | 9842.52 ft (3000 m) without derating | Net Weight | 10.47 lb(US) (4.75 kg) |
Specifications may be subject to change without notice