Key Features
- 1Ensure high reliability with extended mechanical and electrical life. 2、Handle resistive loads up to 1000 Amps and inductive motor applications. 3、Control motors rated up to 800 HP at 480 Vac for demanding tasks. 4、Provide robust motor control and overload protection across industries. 5、Select from various coil voltages including 24v, 120v, and 220v.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Product name | TeSys F |
| Product or Component Type | Contactor | Device short name | LC1F |
| Contactor application | Resistive load<br />Motor control | Utilisation category | AC-3<br />AC-4<br />AC-1 |
| Poles description | 3P | power pole contact composition | 3 NO |
| [Ie] rated operational current | 350 A 104 °F (40 °C)) <= 440 V AC AC-1<br />265 A 131 °F (55 °C)) <= 440 V AC AC-3 | Motor power kW | 132 kW at 380...400 V AC 50/60 Hz (AC-3)<br />140 kW at 415 V AC 50/60 Hz (AC-3)<br />140 kW at 440 V AC 50/60 Hz (AC-3)<br />147 kW at 1000 V AC 50/60 Hz (AC-3)<br />160 kW at 500 V AC 50/60 Hz (AC-3)<br />75 kW at 220...240 V AC 50/60 Hz (AC-3)<br />160 kW at 660...690 V AC 50/60 Hz (AC-3)<br />51 kW at 400 V AC 50/60 Hz (AC-4) |
| [Uc] control circuit voltage | 24...1000 V AC 40...400 Hz with LX1/LX9 coil<br />24...460 V DC with LX4 coil<br />100...250 V AC 50/60 Hz with LXE coil<br />100...380 V with LXE coil | [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III | [Ith] conventional free air thermal current | 350 A (at 104 °F (40 °C)) |
| Irms rated making capacity | 2650 A AC conforming to IEC 60947-4-1 | Rated breaking capacity | 2120 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 2200 A 104 °F (40 °C) - 10 s<br />1230 A 104 °F (40 °C) - 30 s<br />950 A 104 °F (40 °C) - 1 min<br />620 A 104 °F (40 °C) - 3 min<br />480 A 104 °F (40 °C) - 10 min | Associated fuse rating | 315 A aM at <= 440 V<br />400 A gG at <= 440 V |
| Average impedance | 0.3 mOhm - Ith 350 A 50 Hz | [Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C |
| Power dissipation per pole | 37 W AC-1<br />21 W AC-3 | Control circuit voltage limits | Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil<br />Drop-out: 0.35...0.55 Uc AC 40...400 Hz with LX1/LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.15...0.2 Uc DC with LX4 coil<br />Operational: 85...275 V AC 50/60 Hz with LXE coil<br />Drop-out: 0...60 V AC 50/60 Hz with LXE coil<br />Operational: 85...418 V DC with LXE coil<br />Drop-out: 0...45 V DC with LXE coil |
| Heat dissipation | 8 W<br />2.2…2.5 W | Operating time | 40...65 ms closing with LX1/LX9 coil<br />100...170 ms opening with LX1/LX9 coil<br />40...50 ms closing with LX4 coil<br />40...65 ms opening with LX4 coil<br />40...80 ms closing with LXE coil<br />6...54 ms opening with LXE coil |
| Mounting Support | Plate | Standards | IEC 60947-1<br />IEC 60947-4-1<br />JIS C8201-4-1<br />EN 60947-1<br />EN 60947-4-1 |
| Product Certifications | ABS<br />CB<br />DNV<br />RMRoS<br />UL<br />CSA<br />RINA<br />LROS (Lloyds register of shipping)<br />BV<br />UKCA | Connections - terminals | Power circuit bar 2 32 x 4 mm<br />Power circuit lugs-ring terminals 1 0.4 in² (240 mm²)<br />Power circuit connector 1 0.4 in² (240 mm²)<br />Power circuit bolted connection<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1.0 0.0004…0.004 in² (0.25…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1.0 0.0003…0.004 in² (0.2…2.5 mm²)solid without cable end |
| Tightening torque | Power circuit 309.8 lbf.in (35 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)<br />Control circuit 5.3 lbf.in (0.6 N.m) | Mechanical durability | 10 Mcycles |
| Inrush power in VA | 600…700 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />655…803 VA (at 68 °F (20 °C))with LX4 coil<br />300…350 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />300…310 VA (at 68 °F (20 °C))with LXE coil | Hold-in power consumption in VA | 8…10 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />3.68…4.53 VA (at 68 °F (20 °C))with LX4 coil<br />4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil<br />2.5…4.0 VA (at 68 °F (20 °C))with LXE coil |
| Maximum operating rate | 2400 cyc/h 131 °F (55 °C) | Compatibility code | LC1F |
| [Ue] rated operational voltage | <= 1000 V AC-1<br /><= 690 V AC-3<br /><= 690 V AC-4<br /><= 460 V DC | IP degree of protection | IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106 |
| Protective treatment | TH | Ambient Air Temperature for Operation | 23…131 °F (-5…55 °C) |
| Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) | Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) |
| Operating altitude | 9842.52 ft (3000 m) without derating | Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed5 Gn, 5...300 Hz<br />Shocks contactor open6 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms) |
| Height | 8.0 in (203 mm) | Width | 7.9 in (201.5 mm) |
| Depth | 8.4 in (213 mm) | Net Weight | 18.83 lb(US) (8.54 kg) |
Specifications may be subject to change without notice