LC1F265FD
Product ID:32833
Updated: 2026/4/4

Key Features
- 1Control high-power motors up to 132 kW at 400V AC-3. 2、Operate reliably at 2400 cycles/hour in temperatures up to 55°C. 3、Select from versatile coil options for various voltage requirements. 4、Ensure secure connections with robust IP20 screw clamp terminals. 5、Meet environmental standards with RoHS compliance and recyclable design.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Range | TeSys | Range of Product | TeSys F |
| Product or Component Type | Contactor | Device short name | LC1F |
| Contactor application | Resistive load<br />Motor control | Utilisation category | AC-3<br />AC-4<br />AC-1 |
| Poles description | 3P | [Ue] rated operational voltage | <= 1000 V AC-1<br /><= 690 V AC-3<br /><= 690 V AC-4<br /><= 460 V DC |
| [Uc] control circuit voltage | 110 V DC | [Ie] rated operational current | 350 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />265 A (at <131 °F (55 °C)) at <= 440 V AC AC-3 |
| [Uimp] rated impulse withstand voltage | 8 kV | [Ith] conventional free air thermal current | 350 A (at 104 °F (40 °C)) |
| Rated breaking capacity | 2120 A conforming to IEC 60947-4-1 | [Icw] rated short-time withstand current | 2200 A 104 °F (40 °C) - 10 s<br />1230 A 104 °F (40 °C) - 30 s<br />950 A 104 °F (40 °C) - 1 min<br />620 A 104 °F (40 °C) - 3 min<br />480 A 104 °F (40 °C) - 10 min |
| Associated fuse rating | 315 A aM at <= 440 V<br />400 A gG at <= 440 V | Average impedance | 0.3 mOhm - Ith 350 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C | Power dissipation per pole | 37 W AC-1<br />21 W AC-3 |
| Overvoltage category | III | power pole contact composition | 3 NO |
| Motor power kW | 132 kW at 380...400 V AC 50/60 Hz (AC-3)<br />140 kW at 415 V AC 50/60 Hz (AC-3)<br />140 kW at 440 V AC 50/60 Hz (AC-3)<br />160 kW at 500 V AC 50/60 Hz (AC-3)<br />160 kW at 660...690 V AC 50/60 Hz (AC-3)<br />147 kW at 1000 V AC 50/60 Hz (AC-3)<br />75 kW at 220...230 V AC 50/60 Hz (AC-3)<br />51 kW at 400 V AC 50/60 Hz (AC-4) | Control circuit voltage limits | Operational 0.85...1.1 Uc 131 °F (55 °C))<br />Drop-out 0.15...0.2 Uc 131 °F (55 °C)) |
| Mechanical durability | 10 Mcycles | Inrush power in W | 750 W 68 °F (20 °C)) |
| Hold-in power consumption in W | 5 W 68 °F (20 °C) | Maximum operating rate | 2400 cyc/h 131 °F (55 °C) |
| Operating time | 40...50 ms closing<br />40...65 ms opening | Connections - terminals | Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 32 x 4 mm<br />Power circuit lugs-ring terminals 1 0.4 in² (240 mm²)<br />Power circuit connector 1 0.4 in² (240 mm²)<br />Power circuit bolted connection |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m) | Mounting Support | Plate |
| Heat dissipation | 5 W | motor power range | 55…100 kW 200…240 V 3 phase<br />110…220 kW 480…500 V 3 phase<br />110…220 kW 380…440 V 3 phase |
| Motor starter type | Direct on-line contactor | Contactor coil voltage | 110 V DC standard |
| Standards | EN 60947-1<br />IEC 60947-4-1<br />JIS C8201-4-1<br />IEC 60947-1<br />EN 60947-4-1 | Product Certifications | BV<br />ABS<br />CSA<br />CB<br />LROS (Lloyds register of shipping)<br />DNV<br />UL<br />RMRoS<br />RINA<br />UKCA |
| Compatibility code | LC1F | Control circuit type | DC standard |
| IP degree of protection | IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106 | Protective treatment | TH |
| Ambient Air Temperature for Operation | 23…131 °F (-5…55 °C) | Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) |
| Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) | Height | 8.0 in (203 mm) |
| Width | 7.9 in (201.5 mm) | Depth | 8.4 in (213 mm) |
| Operating altitude | 9842.52 ft (3000 m) without derating | Net Weight | 16.40 lb(US) (7.44 kg) |
Specifications may be subject to change without notice